  "heat_rejection": [
    {
      "template": "NREL ZNE Ready 2017",
      "equipment_type": "Closed Cooling Tower",
      "fan_type": "Centrifugal",
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance": 7.0,
      "notes": "From 90.1-2016 Table 6.8.1.7"
    },
    {
      "template": "NREL ZNE Ready 2017",
      "equipment_type": "Closed Cooling Tower",
      "fan_type": "Propeller or Axial",
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance": 16.1,
      "notes": "From 90.1-2016 Table 6.8.1.7"
    },
    {
      "template": "NREL ZNE Ready 2017",
      "equipment_type": "Open Cooling Tower",
      "fan_type": "Centrifugal",
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance": 20.0,
      "notes": "From 90.1-2016 Table 6.8.1.7"
    },
    {
      "template": "NREL ZNE Ready 2017",
      "equipment_type": "Open Cooling Tower",
      "fan_type": "Propeller or Axial",
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance": 40.2,
      "notes": "From 90.1-2016 Table 6.8.1.7"
    }
  ]
}

Version data entries

12 entries across 12 versions & 1 rubygems

Version Path
openstudio-standards-0.2.12 lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/data/nrel_zne_ready_2017.heat_rejection.json
openstudio-standards-0.2.12.rc7 lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/data/nrel_zne_ready_2017.heat_rejection.json
openstudio-standards-0.2.12.rc6 lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/data/nrel_zne_ready_2017.heat_rejection.json
openstudio-standards-0.2.12.rc5 lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/data/nrel_zne_ready_2017.heat_rejection.json
openstudio-standards-0.2.12.rc4 lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/data/nrel_zne_ready_2017.heat_rejection.json
openstudio-standards-0.2.12.rc2 lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/data/nrel_zne_ready_2017.heat_rejection.json
openstudio-standards-0.2.12.rc1 lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/data/nrel_zne_ready_2017.heat_rejection.json
openstudio-standards-0.2.11 lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/data/nrel_zne_ready_2017.heat_rejection.json
openstudio-standards-0.2.11.rc2 lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/data/nrel_zne_ready_2017.heat_rejection.json
openstudio-standards-0.2.11.rc1 lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/data/nrel_zne_ready_2017.heat_rejection.json
openstudio-standards-0.2.10 lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/data/nrel_zne_ready_2017.heat_rejection.json
openstudio-standards-0.2.10.rc3 lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/data/nrel_zne_ready_2017.heat_rejection.json