lib/openstudio-standards/standards/Standards.AirTerminalSingleDuctVAVReheat.rb in openstudio-standards-0.4.0 vs lib/openstudio-standards/standards/Standards.AirTerminalSingleDuctVAVReheat.rb in openstudio-standards-0.5.0.rc1
- old
+ new
@@ -7,13 +7,13 @@
#
# @param air_terminal_single_duct_vav_reheat [OpenStudio::Model::AirTerminalSingleDuctVAVReheat] the air terminal object
# @param zone_min_oa [Double] the zone outdoor air flow rate, in m^3/s.
# If supplied, this will be set as a minimum limit in addition to the minimum
# damper position. EnergyPlus will use the larger of the two values during sizing.
- # @param has_ddc [Bool] whether or not there is DDC control of the VAV terminal,
+ # @param has_ddc [Boolean] whether or not there is DDC control of the VAV terminal,
# which impacts the minimum damper position requirement.
- # @return [Bool] returns true if successful, false if not
+ # @return [Boolean] returns true if successful, false if not
# @todo remove exception where older vintages don't have minimum positions adjusted.
def air_terminal_single_duct_vav_reheat_apply_minimum_damper_position(air_terminal_single_duct_vav_reheat, zone_min_oa = nil, has_ddc = true)
# Minimum damper position
min_damper_position = air_terminal_single_duct_vav_reheat_minimum_damper_position(air_terminal_single_duct_vav_reheat, has_ddc)
air_terminal_single_duct_vav_reheat.setConstantMinimumAirFlowFraction(min_damper_position)
@@ -32,20 +32,20 @@
# Specifies the minimum damper position for VAV dampers.
# Defaults to 30%
#
# @param air_terminal_single_duct_vav_reheat [OpenStudio::Model::AirTerminalSingleDuctVAVReheat] the air terminal object
- # @param has_ddc [Bool] whether or not there is DDC control of the VAV terminal in question
+ # @param has_ddc [Boolean] whether or not there is DDC control of the VAV terminal in question
# @return [Double] minimum damper position
def air_terminal_single_duct_vav_reheat_minimum_damper_position(air_terminal_single_duct_vav_reheat, has_ddc = false)
min_damper_position = 0.3
return min_damper_position
end
# Sets the capacity of the reheat coil based on the minimum flow fraction, and the maximum flow rate.
#
# @param air_terminal_single_duct_vav_reheat [OpenStudio::Model::AirTerminalSingleDuctVAVReheat] the air terminal object
- # @return [Bool] returns true if successful, false if not
+ # @return [Boolean] returns true if successful, false if not
def air_terminal_single_duct_vav_reheat_set_heating_cap(air_terminal_single_duct_vav_reheat)
flow_rate_fraction = 0.0
if air_terminal_single_duct_vav_reheat.constantMinimumAirFlowFraction.is_initialized
flow_rate_fraction = air_terminal_single_duct_vav_reheat.constantMinimumAirFlowFraction.get
end