class Standard
# @!group AirTerminalSingleDuctVAVReheat
- # Set the minimum damper position based on OA
- # rate of the space and the template.
+ # Set the minimum damper position based on OA rate of the space and the template.
# Zones with low OA per area get lower initial guesses.
- # Final position will be adjusted upward
- # as necessary by Standards.AirLoopHVAC.adjust_minimum_vav_damper_positions
+ # Final position will be adjusted upward as necessary by Standards.AirLoopHVAC.adjust_minimum_vav_damper_positions
+ #
+ # @param air_terminal_single_duct_vav_reheat [OpenStudio::Model::AirTerminalSingleDuctVAVReheat] the air terminal object
# @param zone_min_oa [Double] the zone outdoor air flow rate, in m^3/s.
- # If supplied, this will be set as a minimum limit in addition to the minimum
- # damper position. EnergyPlus will use the larger of the two values during sizing.
+ # If supplied, this will be set as a minimum limit in addition to the minimum
+ # damper position. EnergyPlus will use the larger of the two values during sizing.
# @param has_ddc [Bool] whether or not there is DDC control of the VAV terminal,
- # which impacts the minimum damper position requirement.
+ # which impacts the minimum damper position requirement.
# @return [Bool] returns true if successful, false if not
# @todo remove exception where older vintages don't have minimum positions adjusted.
def air_terminal_single_duct_vav_reheat_apply_minimum_damper_position(air_terminal_single_duct_vav_reheat, zone_min_oa = nil, has_ddc = true)
# Minimum damper position
min_damper_position = air_terminal_single_duct_vav_reheat_minimum_damper_position(air_terminal_single_duct_vav_reheat, has_ddc)
@@ -31,37 +31,42 @@
end
# Specifies the minimum damper position for VAV dampers.
# Defaults to 30%
#
+ # @param air_terminal_single_duct_vav_reheat [OpenStudio::Model::AirTerminalSingleDuctVAVReheat] the air terminal object
# @param has_ddc [Bool] whether or not there is DDC control of the VAV terminal in question
+ # @return [Double] minimum damper position
def air_terminal_single_duct_vav_reheat_minimum_damper_position(air_terminal_single_duct_vav_reheat, has_ddc = false)
min_damper_position = 0.3
return min_damper_position
end
- # Sets the capacity of the reheat coil based on the minimum flow fraction,
- # and the maximum flow rate.
+ # Sets the capacity of the reheat coil based on the minimum flow fraction, and the maximum flow rate.
+ #
+ # @param air_terminal_single_duct_vav_reheat [OpenStudio::Model::AirTerminalSingleDuctVAVReheat] the air terminal object
+ # @return [Bool] returns true if successful, false if not
def air_terminal_single_duct_vav_reheat_set_heating_cap(air_terminal_single_duct_vav_reheat)
flow_rate_fraction = 0.0
if air_terminal_single_duct_vav_reheat.constantMinimumAirFlowFraction.is_initialized
flow_rate_fraction = air_terminal_single_duct_vav_reheat.constantMinimumAirFlowFraction.get
end
- if air_terminal_single_duct_vav_reheat.reheatCoil.to_CoilHeatingWater.is_initialized
- reheat_coil = air_terminal_single_duct_vav_reheat.reheatCoil.to_CoilHeatingWater.get
- if reheat_coil.autosizedRatedCapacity.to_f < 1.0e-6
- cap = 1.2 * 1000.0 * flow_rate_fraction * air_terminal_single_duct_vav_reheat.autosizedMaximumAirFlowRate.to_f * (18.0 - 13.0)
- reheat_coil.setPerformanceInputMethod('NominalCapacity')
- reheat_coil.setRatedCapacity(cap)
- air_terminal_single_duct_vav_reheat.setMaximumReheatAirTemperature(18.0)
- end
+ return false unless air_terminal_single_duct_vav_reheat.reheatCoil.to_CoilHeatingWater.is_initialized
+
+ reheat_coil = air_terminal_single_duct_vav_reheat.reheatCoil.to_CoilHeatingWater.get
+ if reheat_coil.autosizedRatedCapacity.to_f < 1.0e-6
+ cap = 1.2 * 1000.0 * flow_rate_fraction * air_terminal_single_duct_vav_reheat.autosizedMaximumAirFlowRate.to_f * (18.0 - 13.0)
+ reheat_coil.setPerformanceInputMethod('NominalCapacity')
+ reheat_coil.setRatedCapacity(cap)
+ air_terminal_single_duct_vav_reheat.setMaximumReheatAirTemperature(18.0)
end
+ return true
end
- # Determines whether the terminal has a NaturalGas,
- # Electricity, or HotWater reheat coil.
- # @return [String] reheat type. One of NaturalGas,
- # Electricity, or HotWater.
+ # Determines whether the terminal has a NaturalGas, Electricity, or HotWater reheat coil.
+ #
+ # @param air_terminal_single_duct_vav_reheat [OpenStudio::Model::AirTerminalSingleDuctVAVReheat] the air terminal object
+ # @return [String] reheat type. One of NaturalGas, Electricity, or HotWater.
def air_terminal_single_duct_vav_reheat_reheat_type(air_terminal_single_duct_vav_reheat)
type = nil
if air_terminal_single_duct_vav_reheat.to_AirTerminalSingleDuctVAVNoReheat.is_initialized
return nil