{ "Settings": { "timeout_seconds": 295, "time_steps_per_hour": 1, "off_grid_flag": false }, "Site": { "roof_squarefeet": null, "renewable_electricity_min_fraction": 0, "renewable_electricity_max_fraction": 1 }, "Financial": { "elec_cost_escalation_rate_fraction": 0.026, "offtaker_discount_rate_fraction": 0.081, "value_of_lost_load_per_kwh": 100.0, "analysis_years": 20, "microgrid_upgrade_cost_fraction": 0.3, "offtaker_tax_rate_fraction": 0.26, "om_cost_escalation_rate_fraction": 0.025 }, "ElectricTariff": { "add_monthly_rates_to_urdb_rate": false, "urdb_label": "63d2f36655296095a0092a6e" }, "ElectricUtility": { "interconnection_limit_kw": 100000000.0, "net_metering_limit_kw": 0.0 }, "ElectricLoad": { "critical_loads_kw_is_net": false, "critical_load_fraction": 0, "loads_kw_is_net": true }, "PV": { "name": "Roof - South Face", "production_incentive_years": 1.0, "location":"roof", "macrs_bonus_fraction": 0.0, "max_kw": 1000000000.0, "production_incentive_max_benefit": 1000000000.0, "radius": 0.0, "state_ibi_fraction": 0.0, "utility_rebate_max": 10000000000.0, "installed_cost_per_kw": 2000.0, "utility_ibi_max": 10000000000.0, "tilt": 10.0, "federal_rebate_per_kw": 0.0, "gcr": 0.4, "production_incentive_max_kw": 1000000000.0, "utility_ibi_fraction": 0.0, "state_ibi_max": 10000000000.0, "state_rebate_per_kw": 0.0, "macrs_option_years": 5, "state_rebate_max": 10000000000.0, "dc_ac_ratio": 1.1, "federal_itc_fraction": 0.3, "production_incentive_per_kwh": 0.0, "module_type": 0, "array_type": 1, "existing_kw": 0.0, "om_cost_per_kw": 16.0, "utility_rebate_per_kw": 0.0, "min_kw": 0.0, "losses": 0.14, "macrs_itc_reduction": 0.5, "degradation_fraction": 0.005, "inv_eff": 0.96, "azimuth": 180.0 }, "Generator": { "production_incentive_years": 0.0, "macrs_bonus_fraction": 0.0, "om_cost_per_kwh": 20.0, "max_kw": 1000000000.0, "production_incentive_max_benefit": 0.0, "state_ibi_fraction": 0.0, "fuel_intercept_gal_per_hr": 0.0125, "generator_only_runs_during_grid_outage": true, "state_rebate_per_kw": 0.0, "installed_cost_per_kw": 2500.0, "utility_ibi_max": 0.0, "fuel_avail_gal": 0.0, "min_turn_down_fraction": 0.3, "production_incentive_max_kw": 0.0, "utility_ibi_fraction": 0.0, "state_ibi_max": 0.0, "fuel_cost_per_gallon": 20.0, "fuel_slope_gal_per_kwh": 0.068, "utility_rebate_max": 0.0, "macrs_option_years": 0, "state_rebate_max": 0.0, "federal_itc_fraction": 0.0, "existing_kw": 0.0, "production_incentive_per_kwh": 0.0, "om_cost_per_kw": 50.0, "utility_rebate_per_kw": 0.0, "min_kw": 0.0, "macrs_itc_reduction": 0.0, "federal_rebate_per_kw": 0.0, "generator_sells_energy_back_to_grid": false }, "Storage": { "max_kwh": 1000000.0, "rectifier_efficiency_fraction": 0.96, "total_itc_fraction": 0.0, "min_kw": 0.0, "max_kw": 1000000.0, "replace_cost_per_kw": 460.0, "replace_cost_per_kwh": 230.0, "min_kwh": 0.0, "installed_cost_per_kw": 1000.0, "total_rebate_per_kw": 0, "installed_cost_per_kwh": 500.0, "inverter_efficiency_fraction": 0.96, "macrs_itc_reduction": 0.5, "canGridCharge": true, "macrs_bonus_fraction": 0.0, "battery_replacement_year": 10, "macrs_option_years": 7, "internal_efficiency_fraction": 0.975, "soc_min_fraction": 0.2, "soc_init_fraction": 0.5, "inverter_replacement_year": 10 } }