{ "heat_rejection": [ { "equipment_type": "Open Cooling Tower", "fan_type": "Centrifugal", "test_fluid": null, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": 20, "minimum_performance_btu_per_hr_per_hp": null }, { "equipment_type": "Open Cooling Tower", "fan_type": "Propeller or Axial", "test_fluid": null, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": 40.2, "minimum_performance_btu_per_hr_per_hp": null }, { "equipment_type": "Closed Cooling Tower", "fan_type": "Centrifugal", "test_fluid": null, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": 7, "minimum_performance_btu_per_hr_per_hp": null }, { "equipment_type": "Closed Cooling Tower", "fan_type": "Propeller or Axial", "test_fluid": null, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": 16.1, "minimum_performance_btu_per_hr_per_hp": null }, { "equipment_type": "Evaporative Condenser", "fan_type": "Centrifugal", "test_fluid": "R-507A", "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": null, "minimum_performance_btu_per_hr_per_hp": 135000 }, { "equipment_type": "Evaporative Condenser", "fan_type": "Propeller or Axial", "test_fluid": "R-507A", "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": null, "minimum_performance_btu_per_hr_per_hp": 157000 }, { "equipment_type": "Evaporative Condenser", "fan_type": "Centrifugal", "test_fluid": "Ammonia", "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": null, "minimum_performance_btu_per_hr_per_hp": 110000 }, { "equipment_type": "Evaporative Condenser", "fan_type": "Propeller or Axial", "test_fluid": "Ammonia", "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": null, "minimum_performance_btu_per_hr_per_hp": 134000 }, { "equipment_type": "Air Cooled Condensers", "fan_type": null, "test_fluid": null, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": null, "minimum_performance_btu_per_hr_per_hp": 176000 }, { "equipment_type": "Dry Cooler", "fan_type": "Propeller or Axial", "test_fluid": null, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": 4, "minimum_performance_btu_per_hr_per_hp": null } ] }