  "heat_pumps": [
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 10.0,
      "pthp_eer_coefficient_2": 0.16,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-1989 Table 10-4A"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 10.0,
      "pthp_eer_coefficient_2": 0.16,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-1989 Table 10-4A"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 10.0,
      "pthp_eer_coefficient_2": 0.16,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-1989 Table 10-4A"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 10.0,
      "pthp_eer_coefficient_2": 0.16,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-1989 Table 10-4A"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 12.3,
      "pthp_eer_coefficient_2": 0.213,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1D"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 12.3,
      "pthp_eer_coefficient_2": 0.213,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1D"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 12.3,
      "pthp_eer_coefficient_2": 0.213,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1D"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 12.3,
      "pthp_eer_coefficient_2": 0.213,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1D"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 12.3,
      "pthp_eer_coefficient_2": 0.213,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1D Before 10/8/2012"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 12.3,
      "pthp_eer_coefficient_2": 0.213,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1D Before 10/8/2012"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2015-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 14.0,
      "pthp_eer_coefficient_2": 0.3,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2013 Table 6.8.1-4"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2015-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 14.0,
      "pthp_eer_coefficient_2": 0.3,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2013 Table 6.8.1-4"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "2016-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 14.0,
      "pthp_eer_coefficient_2": 0.3,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2013 Table 6.8.1-4"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "2016-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 14.0,
      "pthp_eer_coefficient_2": 0.3,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2013 Table 6.8.1-4"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 14.0,
      "pthp_eer_coefficient_2": 0.3,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(3)"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 14.0,
      "pthp_eer_coefficient_2": 0.3,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(3)"
    },
    {
      "template": "CBES Pre-1978",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 10.0,
      "pthp_eer_coefficient_2": 0.16,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "DOE reference model post 1980"
    },
    {
      "template": "CBES Pre-1978",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 10.0,
      "pthp_eer_coefficient_2": 0.16,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "DOE reference model post 1980"
    },
    {
      "template": "CBES T24 1978",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 10.0,
      "pthp_eer_coefficient_2": 0.16,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "DOE reference model pre 1980"
    },
    {
      "template": "CBES T24 1978",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 10.0,
      "pthp_eer_coefficient_2": 0.16,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "DOE reference model pre 1980"
    },
    {
      "template": "CBES T24 1992",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 10.0,
      "pthp_eer_coefficient_2": 0.16,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "DOE reference model post 1980"
    },
    {
      "template": "CBES T24 1992",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 10.0,
      "pthp_eer_coefficient_2": 0.16,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "DOE reference model post 1980"
    },
    {
      "template": "CBES T24 2001",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 12.5,
      "pthp_eer_coefficient_2": 0.213,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2001 Table 1-C2"
    },
    {
      "template": "CBES T24 2001",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 12.5,
      "pthp_eer_coefficient_2": 0.213,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2001 Table 1-C2"
    },
    {
      "template": "CBES T24 2005",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 12.5,
      "pthp_eer_coefficient_2": 0.213,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2005 Table 112-E"
    },
    {
      "template": "CBES T24 2005",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 12.5,
      "pthp_eer_coefficient_2": 0.213,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2005 Table 112-E"
    },
    {
      "template": "CBES T24 2008",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 12.5,
      "pthp_eer_coefficient_2": 0.213,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2008 Table 112-E"
    },
    {
      "template": "CBES T24 2008",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 12.5,
      "pthp_eer_coefficient_2": 0.213,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2008 Table 112-E"
    },
    {
      "template": "DEER Pre-1975",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "PTAC-EIR-fEWB&OAT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PTHP.csv; extracted from MASControl2"
    },
    {
      "template": "DEER 1985",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "PTAC-EIR-fEWB&OAT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PTHP.csv; extracted from MASControl2"
    },
    {
      "template": "DEER 1996",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "PTAC-EIR-fEWB&OAT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PTHP.csv; extracted from MASControl2"
    },
    {
      "template": "DEER 2003",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "PTAC-EIR-fEWB&OAT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PTHP.csv; extracted from MASControl2"
    },
    {
      "template": "DEER 2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "PTAC-EIR-fEWB&OAT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PTHP.csv; extracted from MASControl2"
    },
    {
      "template": "DEER 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "PTAC-EIR-fEWB&OAT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PTHP.csv; extracted from MASControl2"
    },
    {
      "template": "DEER 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.7,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "PTAC-EIR-fEWB&OAT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PTHP.csv; extracted from MASControl2"
    },
    {
      "template": "DEER 2015",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.7,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "PTAC-EIR-fEWB&OAT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PTHP.csv; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "PTAC-EIR-fEWB&OAT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PTHP.csv; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 6.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "PTAC-EIR-fEWB&OAT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PTHP.csv; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 7.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "PTAC-EIR-fEWB&OAT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PTHP.csv; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "PTAC-EIR-fEWB&OAT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PTHP.csv; extracted from MASControl2"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 65000.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 65000.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65001.0,
      "maximum_capacity": 136480.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.26,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65001.0,
      "maximum_capacity": 136480.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.08,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 136481.0,
      "maximum_capacity": 238840.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 136481.0,
      "maximum_capacity": 238840.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.72,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 238841.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 7.94,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 238841.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 7.76,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.6,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.6,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.2,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.0,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.7,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.4,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.5,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.6,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.4,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2014-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2014-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "2015-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "2015-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2015-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.2,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "2016-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 12.2,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2015-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.0,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "2016-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 12.0,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2015-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.7,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "2016-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.6,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2015-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.4,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.5,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "2016-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.4,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.4,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2015-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.6,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "2016-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.6,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2015-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.4,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "2016-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 0.4,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.2,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.0,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.7,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.4,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.5,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.6,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.4,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "CBES Pre-1978",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 6.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 1978Table 6-1"
    },
    {
      "template": "CBES Pre-1978",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 6.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 1978Table 6-1"
    },
    {
      "template": "CBES T24 1978",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 7.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 1978Table 6-1"
    },
    {
      "template": "CBES T24 1978",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 7.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 1978Table 6-1"
    },
    {
      "template": "CBES T24 1992",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 759999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.5,
      "minimum_iplv": 7.5,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 1992 Table 1-C"
    },
    {
      "template": "CBES T24 1992",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 759999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.5,
      "minimum_iplv": 7.5,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 1992 Table 1-C"
    },
    {
      "template": "CBES T24 1992",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 760000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.2,
      "minimum_iplv": 7.5,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 1992 Table 1-C"
    },
    {
      "template": "CBES T24 1992",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 760000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.2,
      "minimum_iplv": 7.5,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 1992 Table 1-C"
    },
    {
      "template": "CBES T24 2001",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2001 Table 1-C1"
    },
    {
      "template": "CBES T24 2001",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2001 Table 1-C1"
    },
    {
      "template": "CBES T24 2001",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2001 Table 1-C1"
    },
    {
      "template": "CBES T24 2001",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2001 Table 1-C1"
    },
    {
      "template": "CBES T24 2001",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2001 Table 1-C1"
    },
    {
      "template": "CBES T24 2001",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2001 Table 1-C1"
    },
    {
      "template": "CBES T24 2005",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2005 Table 112-B"
    },
    {
      "template": "CBES T24 2005",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2005 Table 112-B"
    },
    {
      "template": "CBES T24 2005",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2005 Table 112-B"
    },
    {
      "template": "CBES T24 2005",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2005 Table 112-B"
    },
    {
      "template": "CBES T24 2005",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2005 Table 112-B"
    },
    {
      "template": "CBES T24 2005",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2005 Table 112-B"
    },
    {
      "template": "CBES T24 2008",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2008 Table 112-B"
    },
    {
      "template": "CBES T24 2008",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2008 Table 112-B"
    },
    {
      "template": "CBES T24 2008",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2008 Table 112-B"
    },
    {
      "template": "CBES T24 2008",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2008 Table 112-B"
    },
    {
      "template": "CBES T24 2008",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2008 Table 112-B"
    },
    {
      "template": "CBES T24 2008",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2008 Table 112-B"
    },
    {
      "template": "NREL ZNE Ready 2017",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 16.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Pena Station design guidelines assumptions"
    },
    {
      "template": "DEER Pre-1975",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": 8.265492958,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 1985",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": 8.265492958,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 1996",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": 8.265492958,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 2003",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": 8.265492958,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": 11.07746479,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": 11.07746479,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 58310.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": 10.31875,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpLoSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 2015",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 58310.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": 11.1125,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpLoSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": 11.92957747,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": 11.92957747,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 15.0,
      "minimum_full_load_efficiency": 12.78169014,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 58310.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 15.0,
      "minimum_full_load_efficiency": 11.90625,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpLoSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 58805.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 16.0,
      "minimum_full_load_efficiency": 12.48,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpHiSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpHiSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 58805.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 17.0,
      "minimum_full_load_efficiency": 13.26,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpHiSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpHiSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 65000.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 65000.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65001.0,
      "maximum_capacity": 136480.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.26,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65001.0,
      "maximum_capacity": 136480.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.08,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 136841.0,
      "maximum_capacity": 238840.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 136841.0,
      "maximum_capacity": 238840.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.72,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 238841.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 7.94,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 238841.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 7.76,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.9,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.9,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.2,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.0,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.7,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.4,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.5,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.6,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.4,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2014-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2014-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "2015-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "2015-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 11.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 11.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2015-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.2,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "2016-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 12.2,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2015-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.0,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "2016-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 12.0,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2015-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.7,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "2016-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.6,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2015-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.4,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.5,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "2016-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.4,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.4,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2015-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.6,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "2016-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.6,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2015-12-31T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.4,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "2016-01-01T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 0.4,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 11.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 11.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.2,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.0,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.7,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.4,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.5,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.6,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.4,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "CBES T24 1992",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 759999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.5,
      "minimum_iplv": 7.5,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 1992 Table 1-C"
    },
    {
      "template": "CBES T24 1992",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 759999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.5,
      "minimum_iplv": 7.5,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 1992 Table 1-C"
    },
    {
      "template": "CBES T24 1992",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 760000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.2,
      "minimum_iplv": 7.5,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 1992 Table 1-C"
    },
    {
      "template": "CBES T24 1992",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 760000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.2,
      "minimum_iplv": 7.5,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 1992 Table 1-C"
    },
    {
      "template": "CBES T24 2001",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2001 Table 1-C1"
    },
    {
      "template": "CBES T24 2001",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2001 Table 1-C1"
    },
    {
      "template": "CBES T24 2001",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2001 Table 1-C1"
    },
    {
      "template": "CBES T24 2001",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2001 Table 1-C1"
    },
    {
      "template": "CBES T24 2001",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2001 Table 1-C1"
    },
    {
      "template": "CBES T24 2001",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2001 Table 1-C1"
    },
    {
      "template": "CBES T24 2005",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2005 Table 112-B"
    },
    {
      "template": "CBES T24 2005",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2005 Table 112-B"
    },
    {
      "template": "CBES T24 2005",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2005 Table 112-B"
    },
    {
      "template": "CBES T24 2005",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2005 Table 112-B"
    },
    {
      "template": "CBES T24 2005",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2005 Table 112-B"
    },
    {
      "template": "CBES T24 2005",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2005 Table 112-B"
    },
    {
      "template": "CBES T24 2008",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2008 Table 112-B"
    },
    {
      "template": "CBES T24 2008",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2008 Table 112-B"
    },
    {
      "template": "CBES T24 2008",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2008 Table 112-B"
    },
    {
      "template": "CBES T24 2008",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2008 Table 112-B"
    },
    {
      "template": "CBES T24 2008",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2008 Table 112-B"
    },
    {
      "template": "CBES T24 2008",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Title 24 2008 Table 112-B"
    },
    {
      "template": "NREL ZNE Ready 2017",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 16.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From Pena Station design guidelines assumptions"
    },
    {
      "template": "DEER Pre-1975",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": 8.521126761,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 1985",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": 8.521126761,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 1996",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": 8.521126761,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 2003",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": 8.521126761,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": 11.07746479,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": 11.07746479,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": 11.07746479,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpLoSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 2015",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": 11.92957747,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpLoSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER 2017",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": 11.92957747,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpLoSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": 8.521126761,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": 11.07746479,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": 11.92957747,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 15.0,
      "minimum_full_load_efficiency": 12.78169014,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 34895.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 15.0,
      "minimum_full_load_efficiency": 12.78169014,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC1Sp_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC1Sp_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 58310.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": 10.31875,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpLoSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 58310.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": 11.1125,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpLoSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 58310.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 15.0,
      "minimum_full_load_efficiency": 11.90625,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpLoSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 58805.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 16.0,
      "minimum_full_load_efficiency": 12.48,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpHiSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpHiSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 58805.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 17.0,
      "minimum_full_load_efficiency": 13.26,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpHiSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpHiSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 58805.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 16.0,
      "minimum_full_load_efficiency": 12.48,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpHiSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpHiSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 58805.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 17.0,
      "minimum_full_load_efficiency": 13.26,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpHiSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpHiSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    },
    {
      "template": "DEER High Perf",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 58805.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 18.0,
      "minimum_full_load_efficiency": 14.04,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "SpltAC2SpHiSEER_ClCap_fT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "SpltAC2SpHiSEER_EIR_fT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From DEER PkgAC.csv Subtype = HP; extracted from MASControl2"
    }
  ]
}