{ "heat_pumps": [ { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 65000.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 65000.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 65000.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 65000.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 65001.0, "maximum_capacity": 136480.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.26, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 65001.0, "maximum_capacity": 136480.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.08, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 65001.0, "maximum_capacity": 136480.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.26, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 65001.0, "maximum_capacity": 136480.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.08, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 136481.0, "maximum_capacity": 238840.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 136481.0, "maximum_capacity": 238840.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.72, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 136841.0, "maximum_capacity": 238840.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 136841.0, "maximum_capacity": 238840.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.72, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 238841.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 7.94, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 238841.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 7.76, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 238841.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 7.94, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB 2011", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 238841.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 7.76, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "ThroughWall", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "ThroughWall", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "ThroughWall", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "ThroughWall", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "SmallDuctHighVelocity", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "SmallDuctHighVelocity", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.0, "minimum_iplv": 9.2, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.0, "minimum_iplv": 9.2, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.8, "minimum_iplv": 9.0, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.8, "minimum_iplv": 9.0, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 10.0, "pthp_eer_coefficient_2": 0.16, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-1989 Table 10-4A" }, { "template": "DOE Ref Pre-1980", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 10.0, "pthp_eer_coefficient_2": 0.16, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-1989 Table 10-4A" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "ThroughWall", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "ThroughWall", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "ThroughWall", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "ThroughWall", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "SmallDuctHighVelocity", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "SmallDuctHighVelocity", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.0, "minimum_iplv": 9.2, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.0, "minimum_iplv": 9.2, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.8, "minimum_iplv": 9.0, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.8, "minimum_iplv": 9.0, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 10.0, "pthp_eer_coefficient_2": 0.16, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-1989 Table 10-4A" }, { "template": "DOE Ref 1980-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 10.0, "pthp_eer_coefficient_2": 0.16, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-1989 Table 10-4A" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006" }, { "template": "90.1-2004", "cooling_type": "ThroughWall", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006" }, { "template": "90.1-2004", "cooling_type": "ThroughWall", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006" }, { "template": "90.1-2004", "cooling_type": "ThroughWall", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006" }, { "template": "90.1-2004", "cooling_type": "ThroughWall", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006" }, { "template": "90.1-2004", "cooling_type": "SmallDuctHighVelocity", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B" }, { "template": "90.1-2004", "cooling_type": "SmallDuctHighVelocity", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.0, "minimum_iplv": 9.2, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.0, "minimum_iplv": 9.2, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.8, "minimum_iplv": 9.0, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.8, "minimum_iplv": 9.0, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1B" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 12.3, "pthp_eer_coefficient_2": 0.213, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1D" }, { "template": "90.1-2004", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 12.3, "pthp_eer_coefficient_2": 0.213, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2004 Table 6.8.1D" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006" }, { "template": "90.1-2007", "cooling_type": "ThroughWall", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.9, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006" }, { "template": "90.1-2007", "cooling_type": "ThroughWall", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.9, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006" }, { "template": "90.1-2007", "cooling_type": "ThroughWall", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.6, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006" }, { "template": "90.1-2007", "cooling_type": "ThroughWall", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.6, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.1, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.0, "minimum_iplv": 9.2, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.0, "minimum_iplv": 9.2, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.8, "minimum_iplv": 9.0, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.8, "minimum_iplv": 9.0, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 12.3, "pthp_eer_coefficient_2": 0.213, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1D" }, { "template": "90.1-2007", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 12.3, "pthp_eer_coefficient_2": 0.213, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2007 Table 6.8.1D" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "ThroughWall", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 12.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "ThroughWall", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 12.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "ThroughWall", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 12.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "ThroughWall", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 12.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 11.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.2, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 11.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.2, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.8, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.0, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.8, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.0, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.6, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 10.7, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.6, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 10.7, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.4, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 10.5, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.4, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 10.5, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.5, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 9.6, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.5, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 9.6, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 9.4, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 9.4, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1B" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 12.3, "pthp_eer_coefficient_2": 0.213, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1D Before 10/8/2012" }, { "template": "90.1-2010", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 12.3, "pthp_eer_coefficient_2": 0.213, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1D Before 10/8/2012" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2014-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2014-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2014-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2014-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "2015-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "2015-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "2015-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "2015-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015" }, { "template": "90.1-2013", "cooling_type": "ThroughWall", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 12.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2" }, { "template": "90.1-2013", "cooling_type": "ThroughWall", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 12.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2" }, { "template": "90.1-2013", "cooling_type": "ThroughWall", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 12.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2" }, { "template": "90.1-2013", "cooling_type": "ThroughWall", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 12.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2" }, { "template": "90.1-2013", "cooling_type": "SmallDuctHighVelocity", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 11.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "SmallDuctHighVelocity", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 11.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2015-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 11.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.2, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2015-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 11.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.2, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "2016-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 11.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 12.2, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "2016-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 11.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 12.2, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2015-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.8, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.0, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2015-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.8, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.0, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "2016-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.8, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 12.0, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "2016-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.8, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 12.0, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2015-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.6, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 10.7, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2015-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.6, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 10.7, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "2016-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.6, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.6, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "2016-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.6, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.6, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2015-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.4, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 10.5, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2015-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.4, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 10.5, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "2016-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.4, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.4, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "2016-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.4, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.4, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2015-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.5, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 9.6, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2015-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.5, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 9.6, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "2016-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.5, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 10.6, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "2016-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.5, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 10.6, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2015-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 9.4, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2015-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 9.4, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "2016-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 0.4, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "2016-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 0.4, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2015-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 14.0, "pthp_eer_coefficient_2": 0.3, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2013 Table 6.8.1-4" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2015-12-31T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 14.0, "pthp_eer_coefficient_2": 0.3, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2013 Table 6.8.1-4" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "2016-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 14.0, "pthp_eer_coefficient_2": 0.3, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2013 Table 6.8.1-4" }, { "template": "90.1-2013", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "2016-01-01T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 14.0, "pthp_eer_coefficient_2": 0.3, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From 90.1-2013 Table 6.8.1-4" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "ThroughWall", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 12.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "ThroughWall", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 12.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "ThroughWall", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 12.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "ThroughWall", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 29999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 12.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "SmallDuctHighVelocity", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 11.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "SmallDuctHighVelocity", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 11.0, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 11.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.2, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 11.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.2, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.8, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.0, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 65000.0, "maximum_capacity": 134999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.8, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 11.0, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.6, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 10.7, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.6, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 10.7, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.4, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 10.5, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 135000.0, "maximum_capacity": 239999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.4, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 10.5, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.5, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 9.6, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.5, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 9.6, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 9.4, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 240000.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": 9.4, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 14.0, "pthp_eer_coefficient_2": 0.3, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(3)" }, { "template": "OEESC 2014", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": null, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": 14.0, "pthp_eer_coefficient_2": 0.3, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From OEESC 2014 Table 503.2.3(3)" }, { "template": "NREL ZNE Ready 2017", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 16.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From Pena Station design guidelines assumptions" }, { "template": "NREL ZNE Ready 2017", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 16.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "HPACCoolCapFT", "cool_cap_fflow": "HPACCoolCapFFF", "cool_eir_ft": "HPACCOOLEIRFT", "cool_eir_fflow": "HPACCOOLEIRFFF", "cool_plf_fplr": "HPACCOOLPLFFPLR", "notes": "From Pena Station design guidelines assumptions" }, { "template": "DEER Pre-1975", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT", "cool_cap_fflow": null, "cool_eir_ft": "PTAC-EIR-fEWB&OAT", "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PTHP.csv" }, { "template": "DEER 1985", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT", "cool_cap_fflow": null, "cool_eir_ft": "PTAC-EIR-fEWB&OAT", "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PTHP.csv" }, { "template": "DEER 1996", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT", "cool_cap_fflow": null, "cool_eir_ft": "PTAC-EIR-fEWB&OAT", "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PTHP.csv" }, { "template": "DEER 2003", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT", "cool_cap_fflow": null, "cool_eir_ft": "PTAC-EIR-fEWB&OAT", "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PTHP.csv" }, { "template": "DEER 2007", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT", "cool_cap_fflow": null, "cool_eir_ft": "PTAC-EIR-fEWB&OAT", "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PTHP.csv" }, { "template": "DEER 2011", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT", "cool_cap_fflow": null, "cool_eir_ft": "PTAC-EIR-fEWB&OAT", "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PTHP.csv" }, { "template": "DEER 2014", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.7, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT", "cool_cap_fflow": null, "cool_eir_ft": "PTAC-EIR-fEWB&OAT", "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PTHP.csv" }, { "template": "DEER 2015", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.7, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT", "cool_cap_fflow": null, "cool_eir_ft": "PTAC-EIR-fEWB&OAT", "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PTHP.csv" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 11.9, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT", "cool_cap_fflow": null, "cool_eir_ft": "PTAC-EIR-fEWB&OAT", "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PTHP.csv" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 6.8, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT", "cool_cap_fflow": null, "cool_eir_ft": "PTAC-EIR-fEWB&OAT", "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PTHP.csv" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 7.8, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT", "cool_cap_fflow": null, "cool_eir_ft": "PTAC-EIR-fEWB&OAT", "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PTHP.csv" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "PTHP", "minimum_capacity": 0.0, "maximum_capacity": 9999999.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 8.5, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "PTAC-Cool-Cap-fEWB&OAT", "cool_cap_fflow": null, "cool_eir_ft": "PTAC-EIR-fEWB&OAT", "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PTHP.csv" }, { "template": "DEER Pre-1975", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": 8.265492958, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER Pre-1975", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": 8.521126761, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 1985", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": 8.265492958, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 1985", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": 8.521126761, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 1996", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": 8.265492958, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 1996", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": 8.521126761, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 2003", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 9.7, "minimum_full_load_efficiency": 8.265492958, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 2003", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": 8.521126761, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 2007", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": 11.07746479, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 2007", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": 11.07746479, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 2011", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": 11.07746479, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 2011", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": 11.07746479, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 2014", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 58310.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": 10.31875, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 2014", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": 11.07746479, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 2015", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 58310.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": 11.1125, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 2015", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": 11.92957747, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER 2017", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": 11.92957747, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": 11.92957747, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": 11.92957747, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 15.0, "minimum_full_load_efficiency": 12.78169014, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 58310.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 15.0, "minimum_full_load_efficiency": 11.90625, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 58805.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 16.0, "minimum_full_load_efficiency": 12.48, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC2SpHiSEER_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 58805.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 17.0, "minimum_full_load_efficiency": 13.26, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC2SpHiSEER_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 10.0, "minimum_full_load_efficiency": 8.521126761, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": 11.07746479, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": 11.92957747, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 15.0, "minimum_full_load_efficiency": 12.78169014, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 34895.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 15.0, "minimum_full_load_efficiency": 12.78169014, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC1Sp_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 58310.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 13.0, "minimum_full_load_efficiency": 10.31875, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 58310.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 14.0, "minimum_full_load_efficiency": 11.1125, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 58310.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 15.0, "minimum_full_load_efficiency": 11.90625, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC2SpLoSEER_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 58805.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 16.0, "minimum_full_load_efficiency": 12.48, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC2SpHiSEER_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 58805.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 17.0, "minimum_full_load_efficiency": 13.26, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC2SpHiSEER_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 58805.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 16.0, "minimum_full_load_efficiency": 12.48, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC2SpHiSEER_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 58805.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 17.0, "minimum_full_load_efficiency": 13.26, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC2SpHiSEER_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" }, { "template": "DEER High Perf", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 58805.0, "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": 18.0, "minimum_full_load_efficiency": 14.04, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "SpltAC2SpHiSEER_ClCap_fT", "cool_cap_fflow": null, "cool_eir_ft": null, "cool_eir_fflow": null, "cool_plf_fplr": null, "notes": "From DEER PkgAC.csv Subtype = HP" } ] }