# OpenStudio(R), Copyright (c) 2008-2019, Alliance for Sustainable Energy, LLC.
# All rights reserved.
# Redistribution and use in source and binary forms, with or without
# modification, are permitted provided that the following conditions are met:
#
# (1) Redistributions of source code must retain the above copyright notice,
# this list of conditions and the following disclaimer.
#
# (2) Redistributions in binary form must reproduce the above copyright notice,
# this list of conditions and the following disclaimer in the documentation
# and/or other materials provided with the distribution.
#
# (3) Neither the name of the copyright holder nor the names of any contributors
# may be used to endorse or promote products derived from this software without
# specific prior written permission from the respective party.
#
# (4) Other than as required in clauses (1) and (2), distributions in any form
# of modifications or other derivative works may not use the "OpenStudio"
# trademark, "OS", "os", or any other confusingly similar designation without
# specific prior written permission from Alliance for Sustainable Energy, LLC.
#
# THIS SOFTWARE IS PROVIDED BY THE COPYRIGHT HOLDER(S) AND ANY CONTRIBUTORS
# "AS IS" AND ANY EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO,
# THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE
# ARE DISCLAIMED. IN NO EVENT SHALL THE COPYRIGHT HOLDER(S), ANY CONTRIBUTORS, THE
# UNITED STATES GOVERNMENT, OR THE UNITED STATES DEPARTMENT OF ENERGY, NOR ANY OF
# THEIR EMPLOYEES, BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL,
# EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT
# OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS
# INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT,
# STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY
# OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
# *******************************************************************************

module OsLib_QAQC
  # Check the fan power (W/cfm) for each air loop fan in the model to identify
  # unrealistically sized fans.
  def check_fan_pwr(category, target_standard, max_pwr_delta = 0.1, name_only = false)
    # summary of the check
    check_elems = OpenStudio::AttributeVector.new
    check_elems << OpenStudio::Attribute.new('name', 'Fan Power')
    check_elems << OpenStudio::Attribute.new('category', category)
    check_elems << OpenStudio::Attribute.new('description', 'Check that fan power vs flow makes sense.')

    # stop here if only name is requested this is used to populate display name for arguments
    if name_only == true
      results = []
      check_elems.each do |elem|
        results << elem.valueAsString
      end
      return results
    end

    std = Standard.build(target_standard)

    begin
      # Check each air loop
      @model.getAirLoopHVACs.each do |plant_loop|
        # Set the expected W/cfm
        expected_w_per_cfm = 1.1

        # Check the W/cfm for each fan on each air loop
        plant_loop.supplyComponents.each do |sc|
          # Get the W/cfm for the fan
          obj_type = sc.iddObjectType.valueName.to_s
          case obj_type
          when 'OS_Fan_ConstantVolume'
            actual_w_per_cfm = std.fan_rated_w_per_cfm(sc.to_FanConstantVolume.get)
          when 'OS_Fan_OnOff'
            actual_w_per_cfm = std.fan_rated_w_per_cfm(sc.to_FanOnOff.get)
          when 'OS_Fan_VariableVolume'
            actual_w_per_cfm = std.fan_rated_w_per_cfm(sc.to_FanVariableVolume.get)
          else
            next # Skip non-fan objects
          end

          # Compare W/cfm to expected/typical values
          if ((expected_w_per_cfm - actual_w_per_cfm) / actual_w_per_cfm).abs > max_pwr_delta
            check_elems << OpenStudio::Attribute.new('flag', "For #{sc.name} on #{plant_loop.name}, the actual fan power of #{actual_w_per_cfm.round(1)} W/cfm is more than #{(max_pwr_delta * 100.0).round(2)}% different from the expected #{expected_w_per_cfm} W/cfm.")
          end
        end
      end
    rescue StandardError => e
      # brief description of ruby error
      check_elems << OpenStudio::Attribute.new('flag', "Error prevented QAQC check from running (#{e}).")

      # backtrace of ruby error for diagnostic use
      if @error_backtrace then check_elems << OpenStudio::Attribute.new('flag', e.backtrace.join("\n").to_s) end
    end

    # add check_elms to new attribute
    check_elem = OpenStudio::Attribute.new('check', check_elems)

    return check_elem
    # note: registerWarning and registerValue will be added for checks downstream using os_lib_reporting_qaqc.rb
  end
end