# Custom changes for the SmallDataCenterHighITE prototype. # These are changes that are inconsistent with other prototype building types. module SmallDataCenterHighITE # hvac adjustments specific to the prototype model # # @param model [OpenStudio::Model::Model] OpenStudio model object # @param building_type [String the building type # @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A' # @param prototype_input [Hash] hash of prototype inputs # @return [Boolean] returns true if successful, false if not def model_custom_hvac_tweaks(model, building_type, climate_zone, prototype_input) OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Model', 'Started building type specific adjustments') # add IT equipment (ITE object) for data center building types add_data_center_load(model) # This should be added as a retrofit measure instead of being in the prototype # modify CRAC supply air setpoint manager # modify_crac_sa_stpt_manager(model) OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Model', 'Finished building type specific adjustments') return true end # add IT equipment (ITE object) for data center building types # Normal electric equipment has been added in model_add_load prior to this will replace with ITE object here # # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def add_data_center_load(model) model.getSpaceTypes.each do |space_type| # Get the standards data space_type_properties = space_type_get_standards_data(space_type) elec_equip_have_info = false elec_equip_per_area = space_type_properties['electric_equipment_per_area'].to_f elec_equip_sch = space_type_properties['electric_equipment_schedule'] elec_equip_have_info = true unless elec_equip_per_area.zero? it_fan_power_ratio = 0.4 / (1 + 0.4) # assuming IT fan power is 0.4 of total CPU load if space_type.name.get.downcase.include?('computer') || space_type.name.get.downcase.include?('datacenter') if elec_equip_have_info it_equipment_def = OpenStudio::Model::ElectricEquipmentITEAirCooledDefinition.new(model) it_equipment_def.setName('IT equipment def') it_equipment_def.setWattsperZoneFloorArea(OpenStudio.convert(elec_equip_per_area.to_f, 'W/ft^2', 'W/m^2').get) it_equipment_def.setDesignFanAirFlowRateperPowerInput(0.0001) it_equipment_def.setDesignFanPowerInputFraction(it_fan_power_ratio) it_equipment_def.setDesignEnteringAirTemperature(22.5) # recommended SAT 18-27C, use the middle T as design it_equipment_def.setAirFlowCalculationMethod('FlowControlWithApproachTemperatures') # Set the approach temperatures based on CFD simulation results it_equipment_def.setSupplyTemperatureDifference(9.94) # This is under fully open configuration assumption, based on the lookup table in scorecard it_equipment_def.setReturnTemperatureDifference(-7.21) # This is under fully open configuration assumption, based on the lookup table in scorecard # after the bug in OpenStudio core is fixed, this temperature schedules was enabled it_equipment_def.setSupplyTemperatureDifferenceSchedule(model_add_schedule(model, 'SmallDataCenterHighITE SupplyApproachTemp_SCH')) # This is under fully open configuration assumption, based on the lookup table in scorecard it_equipment_def.setReturnTemperatureDifferenceSchedule(model_add_schedule(model, 'SmallDataCenterHighITE ReturnApproachTemp_SCH')) it_equipment = OpenStudio::Model::ElectricEquipmentITEAirCooled.new(it_equipment_def) it_equipment.setSpaceType(space_type) it_equipment.setName("#{space_type.name} IT equipment") unless elec_equip_sch.nil? it_equipment.setDesignPowerInputSchedule(model_add_schedule(model, elec_equip_sch)) OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.SpaceType', "#{space_type.name} set Design Power Input Schedule to #{elec_equip_sch}.") end it_equipment.setCPULoadingSchedule(model.alwaysOnDiscreteSchedule) end end end # remove normal electric equipment model.getElectricEquipments.each(&:remove) return true end # modify CRAC supply air setpoint manager # # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def modify_crac_sa_stpt_manager(model) supply_temp_sch = get_crac_supply_temp_sch(model) model.getSetpointManagerScheduleds.each do |stpt_manager| next unless stpt_manager.name.to_s.downcase == 'crac supply air setpoint manager' stpt_manager.setSchedule(supply_temp_sch) end return true end # get CRAC supply air temperature schedule # # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [OpenStudio::Model::Schedule] supply temperature schedule object def get_crac_supply_temp_sch(model) supply_temp_diff_max = 0 supply_temp_diff_sch = nil supply_temp_sch = nil model.getElectricEquipmentITEAirCooledDefinitions.each do |it_equip| # if it_equip.supplyTemperatureDifferenceSchedule.is_initialized # # only if supply temperature difference schedule is defined # supply_temp_diff_sch = it_equip.supplyTemperatureDifferenceSchedule.get # if supply_temp_diff_sch.to_ScheduleRuleset.is_initialized # # use the largest supply approach temperature schedule if multiple IT equips are using different schedules # if OpenstudioStandards::Schedules.schedule_ruleset_get_min_max(supply_temp_diff_sch)['max'] <= supply_temp_diff_max # next # else # supply_temp_diff_max = OpenstudioStandards::Schedules.schedule_ruleset_get_min_max(supply_temp_diff_sch)['max'] # supply_temp_diff_sch = supply_temp_diff_sch.to_ScheduleRuleset.get # supply_temp_sch = supply_temp_diff_sch.clone(model).to_ScheduleRuleset.get # supply_temp_sch.setName('AHU Supply Temp Sch updated') # supply_temp_sch.scheduleRules.each do |rule| # day_rule = rule.daySchedule() # day_rule.times().each do |time| # supply_temp_diff = day_rule.getValue(time) # day_rule.addValue(time, it_equip.designEnteringAirTemperature-supply_temp_diff) # end # end # next # skip supply approach temperature if schedule is defined # end # end # end # Take the supply approach temperature at fully open air management scenario supply_temp_diff_max = it_equip.supplyTemperatureDifference if it_equip.supplyTemperatureDifference > supply_temp_diff_max if supply_temp_diff_max > 0 supply_temp_sch = OpenstudioStandards::Schedules.create_constant_schedule_ruleset(model, it_equip.designEnteringAirTemperature - supply_temp_diff_max, name: 'AHU Supply Temp Sch updated', schedule_type_limit: 'Temperature') end end return supply_temp_sch end # swh adjustments specific to the prototype model # # @param model [OpenStudio::Model::Model] OpenStudio model object # @param building_type [String the building type # @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A' # @param prototype_input [Hash] hash of prototype inputs # @return [Boolean] returns true if successful, false if not def model_custom_swh_tweaks(model, building_type, climate_zone, prototype_input) return true end # geometry adjustments specific to the prototype model # # @param model [OpenStudio::Model::Model] OpenStudio model object # @param building_type [String the building type # @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A' # @param prototype_input [Hash] hash of prototype inputs # @return [Boolean] returns true if successful, false if not def model_custom_geometry_tweaks(model, building_type, climate_zone, prototype_input) return true end end