class ASHRAE9012010 < ASHRAE901 # @!group AirTerminalSingleDuctVAVReheat # Set the initial minimum damper position based on OA # rate of the space and the template. # Zones with low OA per area get lower initial guesses. # Final position will be adjusted upward # as necessary by Standards.AirLoopHVAC.apply_minimum_vav_damper_positions # @param zone_oa_per_area [Double] the zone outdoor air per area, m^3/s # @return [Bool] returns true if successful, false if not def air_terminal_single_duct_vav_reheat_apply_initial_prototype_damper_position(air_terminal_single_duct_vav_reheat, building_type, zone_oa_per_area) vav_name = air_terminal_single_duct_vav_reheat.name.get min_damper_position = case air_terminal_single_duct_vav_reheat_reheat_type(air_terminal_single_duct_vav_reheat) when 'HotWater' 0.2 when 'Electricity', 'NaturalGas' 0.3 end # High OA zones # Determine whether or not to use the high minimum guess. # Cutoff was determined by correlating apparent minimum guesses # to OA rates in prototypes since not well documented in papers. if zone_oa_per_area > 0.001 # 0.001 m^3/s*m^2 = .196 cfm/ft2 if building_type == 'Outpatient' min_damper_position = 1.0 elsif building_type == 'Hospital' if vav_name.include? 'PatRoom' min_damper_position = 0.5 else min_damper_position = 1.0 min_damper_position = 1.0 end else min_damper_position = 0.7 end end # Set the minimum flow fraction air_terminal_single_duct_vav_reheat.setConstantMinimumAirFlowFraction(min_damper_position) return true end end