class Standard
  # @!group AirTerminalSingleDuctVAVReheat
  # Set the initial minimum damper position based on OA rate of the space and the template.
  # Defaults to basic behavior, but this method is overridden by all of the ASHRAE-based templates.
  # Zones with low OA per area get lower initial guesses.
  # Final position will be adjusted upward as necessary by Standards.AirLoopHVAC.apply_minimum_vav_damper_positions
  #
  # @param zone_oa_per_area [Double] the zone outdoor air per area, m^3/s
  # @return [Bool] returns true if successful, false if not
  def air_terminal_single_duct_vav_reheat_apply_initial_prototype_damper_position(air_terminal_single_duct_vav_reheat, zone_oa_per_area)
    min_damper_position = 0.3

    # High OA zones
    # Determine whether or not to use the high minimum guess.
    # Cutoff was determined by correlating apparent minimum guesses
    # to OA rates in prototypes since not well documented in papers.
    if zone_oa_per_area > 0.001 # 0.001 m^3/s*m^2 = .196 cfm/ft2
      min_damper_position = 0.7
    end

    # Set the minimum flow fraction
    air_terminal_single_duct_vav_reheat.setConstantMinimumAirFlowFraction(min_damper_position)

    return true
  end
end

Version data entries

11 entries across 11 versions & 1 rubygems

Version Path
openstudio-standards-0.2.10 lib/openstudio-standards/prototypes/common/objects/Prototype.AirTerminalSingleDuctVAVReheat.rb
openstudio-standards-0.2.10.rc3 lib/openstudio-standards/prototypes/common/objects/Prototype.AirTerminalSingleDuctVAVReheat.rb
openstudio-standards-0.2.10.rc2 lib/openstudio-standards/prototypes/common/objects/Prototype.AirTerminalSingleDuctVAVReheat.rb
openstudio-standards-0.2.10.rc1 lib/openstudio-standards/prototypes/common/objects/Prototype.AirTerminalSingleDuctVAVReheat.rb
openstudio-standards-0.2.9 lib/openstudio-standards/prototypes/common/objects/Prototype.AirTerminalSingleDuctVAVReheat.rb
openstudio-standards-0.2.8 lib/openstudio-standards/prototypes/common/objects/Prototype.AirTerminalSingleDuctVAVReheat.rb
openstudio-standards-0.2.7 lib/openstudio-standards/prototypes/common/objects/Prototype.AirTerminalSingleDuctVAVReheat.rb
openstudio-standards-0.2.6 lib/openstudio-standards/prototypes/common/objects/Prototype.AirTerminalSingleDuctVAVReheat.rb
openstudio-standards-0.2.5 lib/openstudio-standards/prototypes/common/objects/Prototype.AirTerminalSingleDuctVAVReheat.rb
openstudio-standards-0.2.4 lib/openstudio-standards/prototypes/common/objects/Prototype.AirTerminalSingleDuctVAVReheat.rb
openstudio-standards-0.2.3 lib/openstudio-standards/prototypes/common/objects/Prototype.AirTerminalSingleDuctVAVReheat.rb