3.0 aedg_office_hvac_wshp_doas aa5fbc1c-4dc2-4a51-84fa-ce5e291f77b6 a5fc87c2-71d2-4d6f-a9e9-590693f0a496 20200401T014105Z 4435983D AedgOfficeHvacWshpDoas AedgOfficeHvacWshpDoas Measure replaces existing HVAC system (if any) with a Water Source Heat Pump (WSHP) with DOAS HVAC system (one DOAS per floor). The WSHP with DOAS system (centralized DOAS, with zone level conditioning) is applied to all space types. In select cases, the user is given the option to preserve existing HVAC schedules. In other cases, new schedules are generated that align with AEDG recommendations. The resulting HVAC system reflects the HVAC recommendations of the 50% Small and Medium Office AEDG. Airloops are dedicated to ventilation (DOAS) and have constant speed fan operation, gas furnace heating, and single speed DX cooling. Conditioning is provided at the zone level with water sourced heat pumps with cycling fans. The heat pumps are connected to a plant loop supplied by a boiler and cooling tower. The heat pump loop floats between 20 C and 30 C. ceilingReturnPlenumSpaceType This space type should be part of a ceiling return air plenum. Choice false false costTotalHVACSystem Total Cost for HVAC System ($). Double true false 0 remake_schedules Apply recommended availability and ventilation schedules for air handlers? Boolean true false true true true false false HVAC.Whole System Measure Type ModelMeasure string Uses SketchUp API false boolean AEDG_HVAC_GenericTestModel_0225_a.osm osm test ED45BF2B README.md.erb erb readmeerb 703C9964 README.md md readme A1E405FB OsLib_AedgMeasures.rb rb resource EDB45706 AedgOfficeHvacWshpDoas_Test.rb rb test 8A8A45DB LICENSE.md md license E0468DD6 OpenStudio 2.0.0 2.8.0 measure.rb rb script 42A9C226