  "tables": [
    {
      "name": "max_total_loop_pump_power",
      "data_type": "table",
      "refs": [
        "NECB 2015 Table 5.2.6.3."
      ],
      "table": [
        {
          "template": "NECB2015",
          "hydronic_system_type": "Heating",
          "total_normalized_pump_power_wperkw": 4.5
        },
        {
          "template": "NECB2015",
          "hydronic_system_type": "Heat_rejection",
          "total_normalized_pump_power_wperkw": 12
        },
        {
          "template": "NECB2015",
          "hydronic_system_type": "Cooling",
          "total_normalized_pump_power_wperkw": 14
        },
        {
          "template": "NECB2015",
          "hydronic_system_type": "WSHP",
          "total_normalized_pump_power_wperkw": 22
        }
      ]
    }
  ]
}

Version data entries

7 entries across 7 versions & 1 rubygems

Version Path
openstudio-standards-0.2.9 lib/openstudio-standards/standards/necb/necb_2015/data/max_pump_powerNECB2015.json
openstudio-standards-0.2.8 lib/openstudio-standards/standards/necb/necb_2015/data/max_pump_powerNECB2015.json
openstudio-standards-0.2.7 lib/openstudio-standards/standards/necb/necb_2015/data/max_pump_powerNECB2015.json
openstudio-standards-0.2.6 lib/openstudio-standards/standards/necb/necb_2015/data/max_pump_powerNECB2015.json
openstudio-standards-0.2.5 lib/openstudio-standards/standards/necb/necb_2015/data/max_pump_powerNECB2015.json
openstudio-standards-0.2.4 lib/openstudio-standards/standards/necb/necb_2015/data/max_pump_powerNECB2015.json
openstudio-standards-0.2.3 lib/openstudio-standards/standards/necb/necb_2015/data/max_pump_powerNECB2015.json