3.0
air_wall_zone_mixing
fd04f73e-a530-4144-9e1e-c1878b1394bc
9080d867-5bc3-4017-bd7c-1be45ba0c771
20191231T201354Z
772B7164
AirWallZoneMixing
Air Wall Zone Mixing
This measure replaces conductive heat transfer with zone mixing wherever air walls are used on matched surfaces or sub-surfaces for walls. A user argument is exposed for a coefficient that represents a target air changes per hour (ACH) for a room where the zone volume/the air wall surface area is the same as its zone height. As the room gets deeper the additional airflow per unit of depth decreases. If two zones have different mixing estimates, the lower will be used. If a smaller portion of an inter-zone wall is an air wall, that will also decrease zone mixing airflow. A construction will be hard assigned to the matched surfaces using the air wall, and the then boundary condition will be changed to adiabatic. This will avoid including both air mixing and conductive transfer across zones. Zone mixing objects will also be made for sub-surface air walls, but they can't be made adiabatic unless their base surface also is. A warning will be issued if that happens
The formula used to determine the design flow rate is the zone mixing coefficient * zone volume/sqrt(zone volume / (air wall area * zone height).
Zone mixing will only be added where there is an air wall and where the matched surfaces belong to spaces in different thermal zones and the base surface type is a wall. Currently floors are not addressed by this measure. Air walls in spaces that are part of the same thermal zone will be left alone. The intended use case is a single base surface that spans the room or one or more sub-surface that spans a portion of it. If you have multiple air wall base surfaces matched between the same zones you may get higher than expected zone mixing.
zone_mixing_coef
Cross Mixing Coefficient
Cross Mixing flow rate = zone mixing coefficient * zone volume/sqrt(thermal zone volume/(air wall area*zone height))
Double
true
false
1
add_zone_mixing_variables
Add Zone Mixing Output Variable Requests
Boolean
true
false
true
true
true
false
false
HVAC.Distribution
Measure Type
ModelMeasure
string
Intended Software Tool
Apply Measure Now
string
Intended Software Tool
OpenStudio Application
string
Intended Software Tool
Parametric Analysis Tool
string
example_model.osm
osm
test
AD3A8B94
SimpleTest.osm
osm
test
38ED88B9
LICENSE.md
md
license
9640B6CB
README.md
md
readme
C272754F
air_wall_zone_mixing_test.rb
rb
test
628E4DB5
example_a.png
png
doc
210227A0
example_b.png
png
doc
F7EB82AD
example_c.png
png
doc
5445EC4B
example_d.png
png
doc
B36DBCB3
measure_logs.png
png
doc
B65B478C
simulation_results.png
png
doc
C7E7739D
timeseries_results.png
png
doc
95902986
os_lib_geometry.rb
rb
resource
FBB26B44
OpenStudio
2.0.0
2.0.0
measure.rb
rb
script
A96950D4