# Custom changes for the Outpatient prototype. # These are changes that are inconsistent with other prototype building types. module Outpatient # hvac adjustments specific to the prototype model # # @param model [OpenStudio::Model::Model] OpenStudio model object # @param building_type [String the building type # @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A' # @param prototype_input [Hash] hash of prototype inputs # @return [Boolean] returns true if successful, false if not def model_custom_hvac_tweaks(model, building_type, climate_zone, prototype_input) OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Model', 'Started Adding HVAC') system_to_space_map = define_hvac_system_map(building_type, climate_zone) # add elevator for the elevator pump room (the fan&lights are already added via standard spreadsheet) add_extra_equip_elevator_pump_room(model) # adjust cooling setpoint at vintages 1B,2B,3B adjust_clg_setpoint(climate_zone, model) # Get the hot water loop hot_water_loop = nil model.getPlantLoops.sort.each do |loop| # If it has a boiler:hotwater, it is the correct loop unless loop.supplyComponents('OS:Boiler:HotWater'.to_IddObjectType).empty? hot_water_loop = loop end end # add humidifier to AHU1 (contains operating room 1) if hot_water_loop add_humidifier(hot_water_loop, model) else OpenStudio.logFree(OpenStudio::Warn, 'openstudio.model.Model', 'Could not find hot water loop to attach humidifier to.') end # adjust minimum damper positions model_adjust_vav_minimum_damper(model) # adjust infiltration for vintages 'DOE Ref Pre-1980', 'DOE Ref 1980-2004' adjust_infiltration(model) # add door infiltration for vertibule add_door_infiltration(climate_zone, model) # reset boiler sizing factor to 0.3 (default 1) reset_boiler_sizing_factor(model) # assign the minimum total air changes to the cooling minimum air flow in Sizing:Zone apply_minimum_total_ach(building_type, model) # set coil sizing if template == '90.1-2004' || template == '90.1-2007' model.getCoilHeatingWaters.each do |coil| if coil.name.to_s == 'PVAV Outpatient F1 Main Htg Coil' || coil.name.to_s == 'PVAV Outpatient F2 F3 Main Htg Coil' coil.setRatedOutletAirTemperature(50.0) end end end # Some exceptions for the Outpatient # @todo Refactor: not sure if this is actually enabled in the original code # if system_name.include? 'PVAV Outpatient F1' # # Outpatient two AHU1 and AHU2 have different HVAC schedule # hvac_op_sch = model_add_schedule(model, 'OutPatientHealthCare AHU1-Fan_Pre2004') # # Outpatient has different temperature settings for sizing # clg_sa_temp_f = 52 # for AHU1 in Outpatient, SAT is 52F # sys_dsn_clg_sa_temp_f = if template == 'DOE Ref 1980-2004' || template == 'DOE Ref Pre-1980' # 52 # else # 45 # end # zn_dsn_clg_sa_temp_f = 52 # zone cooling design SAT # zn_dsn_htg_sa_temp_f = 104 # zone heating design SAT # elsif system_name.include? 'PVAV Outpatient F2 F3' # hvac_op_sch = model_add_schedule(model, 'OutPatientHealthCare AHU2-Fan_Pre2004') # clg_sa_temp_f = 55 # for AHU2 in Outpatient, SAT is 55F # sys_dsn_clg_sa_temp_f = 52 # zn_dsn_clg_sa_temp_f = 55 # zone cooling design SAT # zn_dsn_htg_sa_temp_f = 104 # zone heating design SAT # end OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Model', 'Finished adding HVAC') return true end # add extra equipment for mechanical room # # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def add_extra_equip_elevator_pump_room(model) elevator_pump_room = model.getSpaceByName('Floor 1 Elevator Pump Room').get elec_equip_def = OpenStudio::Model::ElectricEquipmentDefinition.new(model) elec_equip_def.setName('Elevator Pump Room Electric Equipment Definition') elec_equip_def.setFractionLatent(0) elec_equip_def.setFractionRadiant(0.1) elec_equip_def.setFractionLost(0.9) elec_equip_def.setDesignLevel(48_165) elec_equip = OpenStudio::Model::ElectricEquipment.new(elec_equip_def) elec_equip.setName('Elevator Pump Room Elevator Equipment') elec_equip.setSpace(elevator_pump_room) case template when '90.1-2004', '90.1-2007', '90.1-2010', '90.1-2013', '90.1-2016', '90.1-2019' elec_equip.setSchedule(model_add_schedule(model, 'OutPatientHealthCare BLDG_ELEVATORS')) # add elevator fan and lights for 90.1 prototypes elec_equip_def2 = OpenStudio::Model::ElectricEquipmentDefinition.new(model) elec_equip_def2.setName('Elevator Pump Room Electric Equipment Definition2') elec_equip_def2.setFractionLatent(0) elec_equip_def2.setFractionRadiant(0.1) elec_equip_def2.setFractionLost(0.9) case template when '90.1-2004', '90.1-2007' elec_equip_def2.setDesignLevel(485.7) when '90.1-2010' elec_equip_def2.setDesignLevel(317.7) when '90.1-2013', '90.1-2016', '90.1-2019' elec_equip_def2.setDesignLevel(188) end elec_equip2 = OpenStudio::Model::ElectricEquipment.new(elec_equip_def2) elec_equip2.setName('Elevator Lights Fan') elec_equip2.setSpace(elevator_pump_room) case template # light fan schedule for outpatient already exist in the schedule data sheet. when '90.1-2004', '90.1-2007' elec_equip2.setSchedule(model_add_schedule(model, 'OutPatientHealthCare ELEV_LIGHT_FAN_SCH_24_7')) when '90.1-2010', '90.1-2013', '90.1-2016', '90.1-2019' elec_equip2.setSchedule(model_add_schedule(model, 'OutPatientHealthCare ELEV_LIGHT_FAN_SCH_ADD_DF')) end when 'DOE Ref Pre-1980', 'DOE Ref 1980-2004' elec_equip.setSchedule(model_add_schedule(model, 'OutPatientHealthCare BLDG_ELEVATORS_Pre2004')) end return true end # adjust cooling setpoint # # @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A' # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def adjust_clg_setpoint(climate_zone, model) model.getSpaceTypes.sort.each do |space_type| space_type_name = space_type.name.get thermostat_name = space_type_name + ' Thermostat' thermostat = model.getThermostatSetpointDualSetpointByName(thermostat_name).get case template when '90.1-2004', '90.1-2007', '90.1-2010' case climate_zone when 'ASHRAE 169-2006-0B', 'ASHRAE 169-2006-1B', 'ASHRAE 169-2006-2B', 'ASHRAE 169-2006-3B', 'ASHRAE 169-2013-0B', 'ASHRAE 169-2013-1B', 'ASHRAE 169-2013-2B', 'ASHRAE 169-2013-3B' thermostat.setCoolingSetpointTemperatureSchedule(model_add_schedule(model, 'OutPatientHealthCare CLGSETP_SCH_YES_OPTIMUM')) end end end return true end # adjust infiltration # # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def adjust_infiltration(model) case template when 'DOE Ref Pre-1980', 'DOE Ref 1980-2004' model.getSpaces.sort.each do |space| space_type = space.spaceType.get # Skip interior spaces next if OpenstudioStandards::Geometry.space_get_exterior_wall_and_subsurface_area(space) <= 0 # Skip spaces that have no infiltration objects to adjust next if space_type.spaceInfiltrationDesignFlowRates.size <= 0 # get the infiltration information from the space type infiltration infiltration_space_type = space_type.spaceInfiltrationDesignFlowRates[0] infil_sch = infiltration_space_type.schedule.get infil_rate = nil infil_ach = nil if infiltration_space_type.flowperExteriorWallArea.is_initialized infil_rate = infiltration_space_type.flowperExteriorWallArea.get elsif infiltration_space_type.airChangesperHour.is_initialized infil_ach = infiltration_space_type.airChangesperHour.get end # Create an infiltration rate object for this space infiltration = OpenStudio::Model::SpaceInfiltrationDesignFlowRate.new(model) infiltration.setName("#{space.name} Infiltration") infiltration.setFlowperExteriorSurfaceArea(infil_rate) unless infil_rate.nil? || infil_rate.to_f.zero? infiltration.setAirChangesperHour(infil_ach) unless infil_ach.nil? || infil_ach.to_f.zero? infiltration.setSchedule(infil_sch) infiltration.setSpace(space) end model.getSpaceTypes.sort.each do |space_type| space_type.spaceInfiltrationDesignFlowRates.each(&:remove) end else return true end return true end # add door infiltration # # @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A' # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def add_door_infiltration(climate_zone, model) # add extra infiltration for vestibule door case template when 'DOE Ref 1980-2004', 'DOE Ref Pre-1980' return true else vestibule_space = model.getSpaceByName('Floor 1 Vestibule').get infiltration_vestibule_door = OpenStudio::Model::SpaceInfiltrationDesignFlowRate.new(model) infiltration_vestibule_door.setName('Vestibule door Infiltration') infiltration_rate_vestibule_door = 0 case template when '90.1-2004' infiltration_rate_vestibule_door = 1.186002811 infiltration_vestibule_door.setSchedule(model_add_schedule(model, 'OutPatientHealthCare INFIL_Door_Opening_SCH_0.144')) when '90.1-2007', '90.1-2010', '90.1-2013', '90.1-2016', '90.1-2019' case climate_zone when 'ASHRAE 169-2006-0A', 'ASHRAE 169-2006-1A', 'ASHRAE 169-2006-2A', 'ASHRAE 169-2006-2B', 'ASHRAE 169-2013-0A', 'ASHRAE 169-2013-1A', 'ASHRAE 169-2013-2A', 'ASHRAE 169-2013-2B' infiltration_rate_vestibule_door = 1.186002811 infiltration_vestibule_door.setSchedule(model_add_schedule(model, 'OutPatientHealthCare INFIL_Door_Opening_SCH_0.144')) else infiltration_rate_vestibule_door = 0.776824762 infiltration_vestibule_door.setSchedule(model_add_schedule(model, 'OutPatientHealthCare INFIL_Door_Opening_SCH_0.131')) end end infiltration_vestibule_door.setDesignFlowRate(infiltration_rate_vestibule_door) infiltration_vestibule_door.setSpace(vestibule_space) end return true end # add humidifier to AHU1 (contains operating room1) # # @param hot_water_loop [OpenStudio::Model::PlantLoop] hot water loop # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def add_humidifier(hot_water_loop, model) operatingroom1_space = model.getSpaceByName('Floor 1 Operating Room 1').get operatingroom1_zone = operatingroom1_space.thermalZone.get humidistat = OpenStudio::Model::ZoneControlHumidistat.new(model) humidistat.setHumidifyingRelativeHumiditySetpointSchedule(model_add_schedule(model, 'OutPatientHealthCare MinRelHumSetSch')) humidistat.setDehumidifyingRelativeHumiditySetpointSchedule(model_add_schedule(model, 'OutPatientHealthCare MaxRelHumSetSch')) operatingroom1_zone.setZoneControlHumidistat(humidistat) model.getAirLoopHVACs.sort.each do |air_loop| if air_loop.thermalZones.include? operatingroom1_zone humidifier = OpenStudio::Model::HumidifierSteamElectric.new(model) humidifier.setRatedCapacity(3.72E-5) humidifier.setRatedPower(100_000) humidifier.setName("#{air_loop.name.get} Electric Steam Humidifier") # get the water heating coil and add humidifier to the outlet of heating coil (right before fan) htg_coil = nil air_loop.supplyComponents.each do |equip| if equip.to_CoilHeatingWater.is_initialized htg_coil = equip.to_CoilHeatingWater.get end end heating_coil_outlet_node = htg_coil.airOutletModelObject.get.to_Node.get supply_outlet_node = air_loop.supplyOutletNode humidifier.addToNode(heating_coil_outlet_node) humidity_spm = OpenStudio::Model::SetpointManagerSingleZoneHumidityMinimum.new(model) case template when '90.1-2004', '90.1-2007', '90.1-2010', '90.1-2013', '90.1-2016', '90.1-2019' create_coil_heating_electric(model, air_loop_node: supply_outlet_node, name: 'AHU1 extra Electric Htg Coil') create_coil_heating_water(model, hot_water_loop, air_loop_node: supply_outlet_node, name: 'AHU1 extra Water Htg Coil') end # humidity_spm.addToNode(supply_outlet_node) humidity_spm.addToNode(humidifier.outletModelObject.get.to_Node.get) humidity_spm.setControlZone(operatingroom1_zone) end end return true end # for 90.1-2010 Outpatient, AHU2 set minimum outdoor air flow rate as 0 # AHU1 doesn't have economizer # # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def model_modify_oa_controller(model) model.getAirLoopHVACs.sort.each do |air_loop| oa_system = air_loop.airLoopHVACOutdoorAirSystem.get controller_oa = oa_system.getControllerOutdoorAir controller_mv = controller_oa.controllerMechanicalVentilation # AHU1 OA doesn't have controller:mechanicalventilation if air_loop.name.to_s.include? 'Outpatient F1' controller_mv.setAvailabilitySchedule(model.alwaysOffDiscreteSchedule) # add minimum fraction of outdoor air schedule to AHU1 controller_oa.setMinimumFractionofOutdoorAirSchedule(model_add_schedule(model, 'OutPatientHealthCare AHU-1_OAminOAFracSchedule')) # for AHU2, at vintages '90.1-2004', '90.1-2007', '90.1-2010', '90.1-2013', '90.1-2016', '90.1-2019' the minimum OA schedule is not the same as # airloop availability schedule, but separately assigned. elsif template == '90.1-2004' || template == '90.1-2007' || template == '90.1-2010' || template == '90.1-2013' || template == '90.1-2016' || template == '90.1-2019' controller_oa.setMinimumOutdoorAirSchedule(model_add_schedule(model, 'OutPatientHealthCare BLDG_OA_SCH')) # add minimum fraction of outdoor air schedule to AHU2 controller_oa.setMinimumFractionofOutdoorAirSchedule(model_add_schedule(model, 'OutPatientHealthCare BLDG_OA_FRAC_SCH')) end end return true end # adjust room vav damper minimums # # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def model_adjust_vav_minimum_damper(model) # Minimum damper position for Outpatient prototype # Based on AIA 2001 ventilation requirements # See Section 5.2.2.16 in Thornton et al. 2010 # https://www.energycodes.gov/sites/default/files/documents/BECP_Energy_Cost_Savings_STD2010_May2011_v00.pdf init_mdp = { 'FLOOR 1 ANESTHESIA' => 1.0, 'FLOOR 1 CLEAN' => 1.0, 'FLOOR 1 CLEAN WORK' => 1.0, 'FLOOR 1 LOBBY TOILET' => 1.0, 'FLOOR 1 MRI TOILET' => 1.0, 'FLOOR 1 NURSE TOILET' => 1.0, 'FLOOR 1 OPERATING ROOM 1' => 1.0, 'FLOOR 1 OPERATING ROOM 2' => 1.0, 'FLOOR 1 OPERATING ROOM 3' => 1.0, 'FLOOR 1 PACU' => 1.0, 'FLOOR 1 PRE-OP ROOM 1' => 1.0, 'FLOOR 1 PRE-OP ROOM 2' => 1.0, 'FLOOR 1 PRE-OP TOILET' => 1.0, 'FLOOR 1 PROCEDURE ROOM' => 1.0, 'FLOOR 1 RECOVERY ROOM' => 1.0, 'FLOOR 1 SOIL' => 1.0, 'FLOOR 1 SOIL HOLD' => 1.0, 'FLOOR 1 SOIL WORK' => 1.0, 'FLOOR 1 STEP DOWN' => 1.0 } model.getThermalZones.each do |zone| air_terminal = zone.airLoopHVACTerminal if air_terminal.is_initialized air_terminal = air_terminal.get if air_terminal.to_AirTerminalSingleDuctVAVReheat.is_initialized air_terminal = air_terminal.to_AirTerminalSingleDuctVAVReheat.get vav_name = air_terminal.name.get zone_oa_per_area = OpenstudioStandards::ThermalZone.thermal_zone_get_outdoor_airflow_rate_per_area(zone) case template # High OA zones # Determine whether or not to use the high minimum guess. # Cutoff was determined by correlating apparent minimum guesses # to OA rates in prototypes since not well documented in papers. when 'DOE Ref Pre-1980', 'DOE Ref 1980-2004' air_terminal.setConstantMinimumAirFlowFraction(1.0) if vav_name.include?('Floor 1') # Minimum damper position for Outpatient prototype # Based on AIA 2001 ventilation requirements # See Section 5.2.2.16 in Thornton et al. 2010 # https://www.energycodes.gov/sites/default/files/documents/BECP_Energy_Cost_Savings_STD2010_May2011_v00.pdf when '90.1-2004', '90.1-2007', '90.1-2010', '90.1-2013', '90.1-2016', '90.1-2019' zone_name = zone.name.to_s.upcase.gsub(' ZN', '').strip if init_mdp.key? zone_name air_terminal.setConstantMinimumAirFlowFraction(init_mdp[zone_name]) end end end end end return true end # For operating room 1&2 in 2010, 2013, 2016, and 2019 VAV minimum air flow is set by schedule # This is NOT called in model_custom_hvac_tweaks, # instead it is called by model_reset_or_room_vav_minimum_damper AFTER the sizing run, # so that the system is sized at a constant airflow fraction of 1.0, # not 0.3 as defaulted in the zone sizing object # # @param prototype_input [Hash] hash of prototype inputs # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def model_reset_or_room_vav_minimum_damper(prototype_input, model) case template when '90.1-2010', '90.1-2013', '90.1-2016', '90.1-2019' model.getAirTerminalSingleDuctVAVReheats.sort.each do |air_terminal| air_terminal_name = air_terminal.name.get if air_terminal_name.include?('Floor 1 Operating Room 1') || air_terminal_name.include?('Floor 1 Operating Room 2') if model.version < OpenStudio::VersionString.new('3.0.1') air_terminal.setZoneMinimumAirFlowMethod('Scheduled') else air_terminal.setZoneMinimumAirFlowInputMethod('Scheduled') end air_terminal.setMinimumAirFlowFractionSchedule(model_add_schedule(model, 'OutPatientHealthCare OR_MinSA_Sched')) end end end return true end # reset boiler sizing factor # # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def reset_boiler_sizing_factor(model) model.getBoilerHotWaters.sort.each do |boiler| boiler.setSizingFactor(0.3) end return true end # update exhuast fan efficiency # # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def model_update_exhaust_fan_efficiency(model) case template when '90.1-2004', '90.1-2007', '90.1-2010', '90.1-2013', '90.1-2016', '90.1-2019' model.getFanZoneExhausts.sort.each do |exhaust_fan| fan_name = exhaust_fan.name.to_s if (fan_name.include? 'X-Ray') || (fan_name.include? 'MRI Room') exhaust_fan.setFanEfficiency(0.16) exhaust_fan.setPressureRise(125) else exhaust_fan.setFanEfficiency(0.31) exhaust_fan.setPressureRise(249) end end when 'DOE Ref Pre-1980', 'DOE Ref 1980-2004' model.getFanZoneExhausts.sort.each do |exhaust_fan| exhaust_fan.setFanEfficiency(0.338) exhaust_fan.setPressureRise(125) end end return true end # assign the minimum total air changes to the cooling minimum air flow in Sizing:Zone # # @param building_type [String the building type # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def apply_minimum_total_ach(building_type, model) model.getSpaces.sort.each do |space| space_type_name = space.spaceType.get.standardsSpaceType.get search_criteria = { 'template' => template, 'building_type' => building_type, 'space_type' => space_type_name } data = standards_lookup_table_first(table_name: 'space_types', search_criteria: search_criteria) if data.nil? ### OpenStudio.logFree(OpenStudio::Warn, 'openstudio.model.Model', "Could not find data for #{search_criteria}") next end # skip space type without minimum total air changes next if data['minimum_total_air_changes'].nil? # calculate the minimum total air flow minimum_total_ach = data['minimum_total_air_changes'].to_f space_volume = space.volume space_area = space.floorArea minimum_airflow_per_zone = minimum_total_ach * space_volume / 3600 minimum_airflow_per_zone_floor_area = minimum_airflow_per_zone / space_area # add minimum total air flow limit to sizing:zone zone = space.thermalZone.get sizingzone = zone.sizingZone sizingzone.setCoolingDesignAirFlowMethod('DesignDayWithLimit') case template when 'DOE Ref Pre-1980', 'DOE Ref 1980-2004' sizingzone.setCoolingMinimumAirFlow(minimum_airflow_per_zone) when '90.1-2004', '90.1-2007', '90.1-2010', '90.1-2013', '90.1-2016', '90.1-2019' sizingzone.setCoolingMinimumAirFlowperZoneFloorArea(minimum_airflow_per_zone_floor_area) end end return true end # swh adjustments specific to the prototype model # # @param model [OpenStudio::Model::Model] OpenStudio model object # @param building_type [String the building type # @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A' # @param prototype_input [Hash] hash of prototype inputs # @return [Boolean] returns true if successful, false if not def model_custom_swh_tweaks(model, building_type, climate_zone, prototype_input) return true end # geometry adjustments specific to the prototype model # # @param model [OpenStudio::Model::Model] OpenStudio model object # @param building_type [String the building type # @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A' # @param prototype_input [Hash] hash of prototype inputs # @return [Boolean] returns true if successful, false if not def model_custom_geometry_tweaks(model, building_type, climate_zone, prototype_input) # Set original building North axis OpenstudioStandards::Geometry.model_set_building_north_axis(model, 0.0) return true end # @!group AirTerminalSingleDuctVAVReheat # Set the initial minimum damper position based on OA rate of the space and the template. # Zones with low OA per area get lower initial guesses. # Final position will be adjusted upward as necessary by Standards.AirLoopHVAC.apply_minimum_vav_damper_positions # # @param air_terminal_single_duct_vav_reheat [OpenStudio::Model::AirTerminalSingleDuctVAVReheat] the air terminal object # @param zone_oa_per_area [Double] the zone outdoor air per area in m^3/s*m^2 # @return [Boolean] returns true if successful, false if not def air_terminal_single_duct_vav_reheat_apply_initial_prototype_damper_position(air_terminal_single_duct_vav_reheat, zone_oa_per_area) # Minimum damper position # Based on AIA 2001 ventilation requirements # See Section 5.2.2.16 in Thornton et al. 2010 # https://www.energycodes.gov/sites/default/files/documents/BECP_Energy_Cost_Savings_STD2010_May2011_v00.pdf if template == '90.1-2004' || template == '90.1-2007' min_damper_position = 0.3 init_mdp = { 'FLOOR 2 CONFERENCE TOILET' => 1.0, 'FLOOR 2 EXAM 1' => 1.0, 'FLOOR 2 EXAM 2' => 1.0, 'FLOOR 2 EXAM 3' => 1.0, 'FLOOR 2 EXAM 4' => 1.0, 'FLOOR 2 EXAM 5' => 1.0, 'FLOOR 2 EXAM 6' => 1.0, 'FLOOR 2 EXAM 7' => 1.0, 'FLOOR 2 EXAM 8' => 1.0, 'FLOOR 2 EXAM 9' => 1.0, 'FLOOR 2 RECEPTION TOILET' => 1.0, 'FLOOR 2 WORK TOILET' => 1.0, 'FLOOR 3 LOUNGE TOILET' => 1.0, 'FLOOR 3 OFFICE TOILET' => 1.0, 'FLOOR 3 PHYSICAL THERAPY 1' => 1.0, 'FLOOR 3 PHYSICAL THERAPY 2' => 1.0, 'FLOOR 3 PHYSICAL THERAPY TOILET' => 1.0, 'FLOOR 3 STORAGE 1' => 1.0, 'FLOOR 3 TREATMENT' => 1.0 } elsif template == '90.1-2010' || template == '90.1-2013' || template == '90.1-2016' || template == '90.1-2019' min_damper_position = 0.2 init_mdp = { 'FLOOR 2 CONFERENCE TOILET' => 1.0, 'FLOOR 2 EXAM 1' => 0.51, 'FLOOR 2 EXAM 2' => 1.0, 'FLOOR 2 EXAM 3' => 1.0, 'FLOOR 2 EXAM 4' => 0.64, 'FLOOR 2 EXAM 5' => 0.69, 'FLOOR 2 EXAM 6' => 0.94, 'FLOOR 2 EXAM 7' => 1.0, 'FLOOR 2 EXAM 8' => 0.93, 'FLOOR 2 EXAM 9' => 1.0, 'FLOOR 2 RECEPTION TOILET' => 1.0, 'FLOOR 2 WORK TOILET' => 1.0, 'FLOOR 3 LOUNGE TOILET' => 1.0, 'FLOOR 3 OFFICE TOILET' => 1.0, 'FLOOR 3 PHYSICAL THERAPY 1' => 0.69, 'FLOOR 3 PHYSICAL THERAPY 2' => 0.83, 'FLOOR 3 PHYSICAL THERAPY TOILET' => 1.0, 'FLOOR 3 STORAGE 1' => 1.0, 'FLOOR 3 TREATMENT' => 0.81 } end if !init_mdp.nil? airlp = air_terminal_single_duct_vav_reheat.airLoopHVAC.get init_mdp.each do |zn_name, mdp| if air_terminal_single_duct_vav_reheat.name.to_s.upcase.strip.include? zn_name.to_s.strip min_damper_position = mdp end end else min_damper_position = 0.3 end # Set the minimum flow fraction air_terminal_single_duct_vav_reheat.setConstantMinimumAirFlowFraction(min_damper_position) return true end # Type of SAT reset for this building type # # @param air_loop_hvac [OpenStudio::Model::AirLoopHVAC] air loop # @return [String] Returns type of SAT reset def air_loop_hvac_supply_air_temperature_reset_type(air_loop_hvac) return 'oa' end end