class ASHRAE9012010 < ASHRAE901 # @!group AirLoopHVAC # Apply multizone vav outdoor air method and # adjust multizone VAV damper positions # to achieve a system minimum ventilation effectiveness # of 0.6 per PNNL. Hard-size the resulting min OA # into the sizing:system object. # # return [Bool] returns true if successful, false if not # @todo move building-type-specific code to Prototype classes def air_loop_hvac_apply_multizone_vav_outdoor_air_sizing(air_loop_hvac) # First time adjustment: # Only applies to multi-zone vav systems # exclusion: for Outpatient: (1) both AHU1 and AHU2 in 'DOE Ref Pre-1980' and 'DOE Ref 1980-2004' # (2) AHU1 in 2004-2013 # TODO refactor: move building-type-specific code to Prototype classes if air_loop_hvac_multizone_vav_system?(air_loop_hvac) && !(air_loop_hvac.name.to_s.include? 'Outpatient F1') air_loop_hvac_adjust_minimum_vav_damper_positions(air_loop_hvac) end # Second time adjustment: # Only apply to 2010 and 2013 Outpatient (both AHU1 and AHU2) # TODO maybe apply to hospital as well? # TODO refactor: move building-type-specific code to Prototype classes if air_loop_hvac.name.to_s.include? 'Outpatient' air_loop_hvac_adjust_minimum_vav_damper_positions_outpatient(air_loop_hvac) end return true end # Determine the limits for the type of economizer present # on the AirLoopHVAC, if any. # @return [Array] [drybulb_limit_f, enthalpy_limit_btu_per_lb, dewpoint_limit_f] def air_loop_hvac_economizer_limits(air_loop_hvac, climate_zone) drybulb_limit_f = nil enthalpy_limit_btu_per_lb = nil dewpoint_limit_f = nil # Get the OA system and OA controller oa_sys = air_loop_hvac.airLoopHVACOutdoorAirSystem if oa_sys.is_initialized oa_sys = oa_sys.get else return [nil, nil, nil] # No OA system end oa_control = oa_sys.getControllerOutdoorAir economizer_type = oa_control.getEconomizerControlType case economizer_type when 'NoEconomizer' return [nil, nil, nil] when 'FixedDryBulb' case climate_zone when 'ASHRAE 169-2006-1B', 'ASHRAE 169-2006-2B', 'ASHRAE 169-2006-3B', 'ASHRAE 169-2006-3C', 'ASHRAE 169-2006-4B', 'ASHRAE 169-2006-4C', 'ASHRAE 169-2006-5B', 'ASHRAE 169-2006-5C', 'ASHRAE 169-2006-6B', 'ASHRAE 169-2006-7A', 'ASHRAE 169-2006-7B', 'ASHRAE 169-2006-8A', 'ASHRAE 169-2006-8B' drybulb_limit_f = 75 when 'ASHRAE 169-2006-5A', 'ASHRAE 169-2006-6A' drybulb_limit_f = 70 end when 'FixedEnthalpy' enthalpy_limit_btu_per_lb = 28 when 'FixedDewPointAndDryBulb' drybulb_limit_f = 75 dewpoint_limit_f = 55 end return [drybulb_limit_f, enthalpy_limit_btu_per_lb, dewpoint_limit_f] end # Determine if the system economizer must be integrated or not. # All economizers must be integrated in 90.1-2010 def air_loop_hvac_integrated_economizer_required?(air_loop_hvac, climate_zone) integrated_economizer_required = true return integrated_economizer_required end # Check the economizer type currently specified in the ControllerOutdoorAir object on this air loop # is acceptable per the standard. # # @param (see #economizer_required?) # @return [Bool] Returns true if allowable, if the system has no economizer or no OA system. # Returns false if the economizer type is not allowable. def air_loop_hvac_economizer_type_allowable?(air_loop_hvac, climate_zone) # EnergyPlus economizer types # 'NoEconomizer' # 'FixedDryBulb' # 'FixedEnthalpy' # 'DifferentialDryBulb' # 'DifferentialEnthalpy' # 'FixedDewPointAndDryBulb' # 'ElectronicEnthalpy' # 'DifferentialDryBulbAndEnthalpy' # Get the OA system and OA controller oa_sys = air_loop_hvac.airLoopHVACOutdoorAirSystem if oa_sys.is_initialized oa_sys = oa_sys.get else return true # No OA system end oa_control = oa_sys.getControllerOutdoorAir economizer_type = oa_control.getEconomizerControlType # Return true if no economizer is present if economizer_type == 'NoEconomizer' return true end # Determine the prohibited types prohibited_types = [] case climate_zone when 'ASHRAE 169-2006-1B', 'ASHRAE 169-2006-2B', 'ASHRAE 169-2006-3B', 'ASHRAE 169-2006-3C', 'ASHRAE 169-2006-4B', 'ASHRAE 169-2006-4C', 'ASHRAE 169-2006-5B', 'ASHRAE 169-2006-6B', 'ASHRAE 169-2006-7A', 'ASHRAE 169-2006-7B', 'ASHRAE 169-2006-8A', 'ASHRAE 169-2006-8B' prohibited_types = ['FixedEnthalpy'] when 'ASHRAE 169-2006-1A', 'ASHRAE 169-2006-2A', 'ASHRAE 169-2006-3A', 'ASHRAE 169-2006-4A' prohibited_types = ['FixedDryBulb', 'DifferentialDryBulb'] when 'ASHRAE 169-2006-5A', 'ASHRAE 169-2006-6A', prohibited_types = [] end # Check if the specified type is allowed economizer_type_allowed = true if prohibited_types.include?(economizer_type) economizer_type_allowed = false end return economizer_type_allowed end # Determine if multizone vav optimization is required. # # @param (see #economizer_required?) # @return [Bool] Returns true if required, false if not. # @todo Add exception logic for # systems with AIA healthcare ventilation requirements # dual duct systems def air_loop_hvac_multizone_vav_optimization_required?(air_loop_hvac, climate_zone) multizone_opt_required = false # Not required for systems with fan-powered terminals num_fan_powered_terminals = 0 air_loop_hvac.demandComponents.each do |comp| if comp.to_AirTerminalSingleDuctParallelPIUReheat.is_initialized || comp.to_AirTerminalSingleDuctSeriesPIUReheat.is_initialized num_fan_powered_terminals += 1 end end if num_fan_powered_terminals > 0 OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}, multizone vav optimization is not required because the system has #{num_fan_powered_terminals} fan-powered terminals.") return multizone_opt_required end # Not required for systems that require an ERV if air_loop_hvac_energy_recovery?(air_loop_hvac) OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}: multizone vav optimization is not required because the system has Energy Recovery.") return multizone_opt_required end # Get the OA intake controller_oa = nil controller_mv = nil oa_system = nil if air_loop_hvac.airLoopHVACOutdoorAirSystem.is_initialized oa_system = air_loop_hvac.airLoopHVACOutdoorAirSystem.get controller_oa = oa_system.getControllerOutdoorAir controller_mv = controller_oa.controllerMechanicalVentilation else OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}, multizone optimization is not applicable because system has no OA intake.") return multizone_opt_required end # Get the AHU design supply air flow rate dsn_flow_m3_per_s = nil if air_loop_hvac.designSupplyAirFlowRate.is_initialized dsn_flow_m3_per_s = air_loop_hvac.designSupplyAirFlowRate.get elsif air_loop_hvac.autosizedDesignSupplyAirFlowRate.is_initialized dsn_flow_m3_per_s = air_loop_hvac.autosizedDesignSupplyAirFlowRate.get else OpenStudio.logFree(OpenStudio::Warn, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name} design supply air flow rate is not available, cannot apply efficiency standard.") return multizone_opt_required end dsn_flow_cfm = OpenStudio.convert(dsn_flow_m3_per_s, 'm^3/s', 'cfm').get # Get the minimum OA flow rate min_oa_flow_m3_per_s = nil if controller_oa.minimumOutdoorAirFlowRate.is_initialized min_oa_flow_m3_per_s = controller_oa.minimumOutdoorAirFlowRate.get elsif controller_oa.autosizedMinimumOutdoorAirFlowRate.is_initialized min_oa_flow_m3_per_s = controller_oa.autosizedMinimumOutdoorAirFlowRate.get else OpenStudio.logFree(OpenStudio::Warn, 'openstudio.standards.AirLoopHVAC', "For #{controller_oa.name}: minimum OA flow rate is not available, cannot apply efficiency standard.") return multizone_opt_required end min_oa_flow_cfm = OpenStudio.convert(min_oa_flow_m3_per_s, 'm^3/s', 'cfm').get # Calculate the percent OA at design airflow pct_oa = min_oa_flow_m3_per_s / dsn_flow_m3_per_s # Not required for systems where # exhaust is more than 70% of the total OA intake. if pct_oa > 0.7 OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{controller_oa.name}: multizone optimization is not applicable because system is more than 70% OA.") return multizone_opt_required end # TODO: Not required for dual-duct systems # if self.isDualDuct # OpenStudio::logFree(OpenStudio::Info, "openstudio.standards.AirLoopHVAC", "For #{controller_oa.name}: multizone optimization is not applicable because it is a dual duct system") # return multizone_opt_required # end # If here, multizone vav optimization is required multizone_opt_required = true return multizone_opt_required end # Determines the OA flow rates above which an economizer is required. # Two separate rates, one for systems with an economizer and another # for systems without. # are zero for both types. # @return [Array] [min_oa_without_economizer_cfm, min_oa_with_economizer_cfm] def air_loop_hvac_demand_control_ventilation_limits(air_loop_hvac) min_oa_without_economizer_cfm = 3000 min_oa_with_economizer_cfm = 1200 return [min_oa_without_economizer_cfm, min_oa_with_economizer_cfm] end # Determine the air flow and number of story limits # for whether motorized OA damper is required. # @return [Array] [minimum_oa_flow_cfm, maximum_stories] def air_loop_hvac_motorized_oa_damper_limits(air_loop_hvac, climate_zone) case climate_zone when 'ASHRAE 169-2006-1A', 'ASHRAE 169-2006-1B', 'ASHRAE 169-2006-2A', 'ASHRAE 169-2006-2B', 'ASHRAE 169-2006-3A', 'ASHRAE 169-2006-3B', 'ASHRAE 169-2006-3C', minimum_oa_flow_cfm = 300 maximum_stories = 999 # Any number of stories else minimum_oa_flow_cfm = 300 maximum_stories = 0 end return [minimum_oa_flow_cfm, maximum_stories] end # Determine the number of stages that should be used as controls # for single zone DX systems. 90.1-2010 depends on the cooling # capacity of the system. # # @return [Integer] the number of stages: 0, 1, 2 def air_loop_hvac_single_zone_controls_num_stages(air_loop_hvac, climate_zone) min_clg_cap_btu_per_hr = 65_000 clg_cap_btu_per_hr = OpenStudio.convert(air_loop_hvac_total_cooling_capacity(air_loop_hvac), 'W', 'Btu/hr').get if clg_cap_btu_per_hr >= min_clg_cap_btu_per_hr num_stages = 2 OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}: two-stage control is required since cooling capacity of #{clg_cap_btu_per_hr.round} Btu/hr exceeds the minimum of #{min_clg_cap_btu_per_hr.round} Btu/hr .") else num_stages = 1 OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}: two-stage control is not required since cooling capacity of #{clg_cap_btu_per_hr.round} Btu/hr is less than the minimum of #{min_clg_cap_btu_per_hr.round} Btu/hr .") end return num_stages end # Determine if the system required supply air temperature # (SAT) reset. For 90.1-2010, SAT reset requirements are based on climate zone. # # @param (see #economizer_required?) # @return [Bool] Returns true if required, false if not. def air_loop_hvac_supply_air_temperature_reset_required?(air_loop_hvac, climate_zone) is_sat_reset_required = false # Only required for multizone VAV systems unless air_loop_hvac_multizone_vav_system?(air_loop_hvac) return is_sat_reset_required end case climate_zone when 'ASHRAE 169-2006-1A', 'ASHRAE 169-2006-2A', 'ASHRAE 169-2006-3A' OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}: Supply air temperature reset is not required per 6.5.3.4 Exception 1, the system is located in climate zone #{climate_zone}.") return is_sat_reset_required when 'ASHRAE 169-2006-1B', 'ASHRAE 169-2006-2B', 'ASHRAE 169-2006-3B', 'ASHRAE 169-2006-3C', 'ASHRAE 169-2006-4A', 'ASHRAE 169-2006-4B', 'ASHRAE 169-2006-4C', 'ASHRAE 169-2006-5A', 'ASHRAE 169-2006-5B', 'ASHRAE 169-2006-5C', 'ASHRAE 169-2006-6A', 'ASHRAE 169-2006-6B', 'ASHRAE 169-2006-7A', 'ASHRAE 169-2006-7B', 'ASHRAE 169-2006-8A', 'ASHRAE 169-2006-8B' is_sat_reset_required = true OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}: Supply air temperature reset is required.") return is_sat_reset_required end end # Determine the airflow limits that govern whether or not # an ERV is required. Based on climate zone and % OA. # @return [Double] the flow rate above which an ERV is required. # if nil, ERV is never required. def air_loop_hvac_energy_recovery_ventilator_flow_limit(air_loop_hvac, climate_zone, pct_oa) # Table 6.5.6.1 case climate_zone when 'ASHRAE 169-2006-3B', 'ASHRAE 169-2006-3C', 'ASHRAE 169-2006-4B', 'ASHRAE 169-2006-4C', 'ASHRAE 169-2006-5B' if pct_oa < 0.3 erv_cfm = nil elsif pct_oa >= 0.3 && pct_oa < 0.4 erv_cfm = nil elsif pct_oa >= 0.4 && pct_oa < 0.5 erv_cfm = nil elsif pct_oa >= 0.5 && pct_oa < 0.6 erv_cfm = nil elsif pct_oa >= 0.6 && pct_oa < 0.7 erv_cfm = nil elsif pct_oa >= 0.7 && pct_oa < 0.8 erv_cfm = 5000 elsif pct_oa >= 0.8 erv_cfm = 5000 end when 'ASHRAE 169-2006-1B', 'ASHRAE 169-2006-2B', 'ASHRAE 169-2006-5C' if pct_oa < 0.3 erv_cfm = nil elsif pct_oa >= 0.3 && pct_oa < 0.4 erv_cfm = nil elsif pct_oa >= 0.4 && pct_oa < 0.5 erv_cfm = nil elsif pct_oa >= 0.5 && pct_oa < 0.6 erv_cfm = 26_000 elsif pct_oa >= 0.6 && pct_oa < 0.7 erv_cfm = 12_000 elsif pct_oa >= 0.7 && pct_oa < 0.8 erv_cfm = 5000 elsif pct_oa >= 0.8 erv_cfm = 4000 end when 'ASHRAE 169-2006-6B' if pct_oa < 0.3 erv_cfm = nil elsif pct_oa >= 0.3 && pct_oa < 0.4 erv_cfm = 11_000 elsif pct_oa >= 0.4 && pct_oa < 0.5 erv_cfm = 5500 elsif pct_oa >= 0.5 && pct_oa < 0.6 erv_cfm = 4500 elsif pct_oa >= 0.6 && pct_oa < 0.7 erv_cfm = 3500 elsif pct_oa >= 0.7 && pct_oa < 0.8 erv_cfm = 2500 elsif pct_oa >= 0.8 erv_cfm = 1500 end when 'ASHRAE 169-2006-1A', 'ASHRAE 169-2006-2A', 'ASHRAE 169-2006-3A', 'ASHRAE 169-2006-4A', 'ASHRAE 169-2006-5A', 'ASHRAE 169-2006-6A' if pct_oa < 0.3 erv_cfm = nil elsif pct_oa >= 0.3 && pct_oa < 0.4 erv_cfm = 5500 elsif pct_oa >= 0.4 && pct_oa < 0.5 erv_cfm = 4500 elsif pct_oa >= 0.5 && pct_oa < 0.6 erv_cfm = 3500 elsif pct_oa >= 0.6 && pct_oa < 0.7 erv_cfm = 2000 elsif pct_oa >= 0.7 && pct_oa < 0.8 erv_cfm = 1000 elsif pct_oa >= 0.8 erv_cfm = 0 end when 'ASHRAE 169-2006-7A', 'ASHRAE 169-2006-7B', 'ASHRAE 169-2006-8A', 'ASHRAE 169-2006-8B' if pct_oa < 0.3 erv_cfm = nil elsif pct_oa >= 0.3 && pct_oa < 0.4 erv_cfm = 2500 elsif pct_oa >= 0.4 && pct_oa < 0.5 erv_cfm = 1000 elsif pct_oa >= 0.5 && pct_oa < 0.6 erv_cfm = 0 elsif pct_oa >= 0.6 && pct_oa < 0.7 erv_cfm = 0 elsif pct_oa >= 0.7 && pct_oa < 0.8 erv_cfm = 0 elsif pct_oa >= 0.8 erv_cfm = 0 end end return erv_cfm end end