  "heat_pumps_heating": [
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 65000.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": 8.9,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 65000.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": 8.9,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 65001.0,
      "maximum_capacity": 238840.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": 9.5,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "subcategory": "Split System",
      "minimum_capacity": 65001.0,
      "maximum_capacity": 238840.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": 9.5,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 238841.0,
      "maximum_capacity": 9999999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": 9.2,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "subcategory": "Split System",
      "minimum_capacity": 238841.0,
      "maximum_capacity": 9999999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": 9.2,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 6.8,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 since no DOE Reference Buildings had heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 6.6,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 since no DOE Reference Buildings had heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "ThroughWall",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_heating_seasonal_performance_factor": 6.8,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 since no DOE Reference Buildings had heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "ThroughWall",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_heating_seasonal_performance_factor": 6.6,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 since no DOE Reference Buildings had heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "SmallDuctHighVelocity",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 6.8,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 since no DOE Reference Buildings had heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": 3.2,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 since no DOE Reference Buildings had heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 9999999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": 3.1,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 since no DOE Reference Buildings had heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 6.8,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 since no DOE Reference Buildings had heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 6.6,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 since no DOE Reference Buildings had heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "ThroughWall",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_heating_seasonal_performance_factor": 6.8,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 since no DOE Reference Buildings had heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "ThroughWall",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_heating_seasonal_performance_factor": 6.6,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 since no DOE Reference Buildings had heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "SmallDuctHighVelocity",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 6.8,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 since no DOE Reference Buildings had heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": 3.2,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 since no DOE Reference Buildings had heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 9999999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": 3.1,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 since no DOE Reference Buildings had heat pumps"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 6.8,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 6.6,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "ThroughWall",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_heating_seasonal_performance_factor": 6.8,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "ThroughWall",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_heating_seasonal_performance_factor": 6.6,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "SmallDuctHighVelocity",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 6.8,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": 3.2,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 9999999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": 3.1,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 7.7,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 7.7,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "ThroughWall",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_heating_seasonal_performance_factor": 7.1,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "ThroughWall",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_heating_seasonal_performance_factor": 7.0,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": 3.2,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 9999999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": 3.1,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 7.7,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 7.7,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "ThroughWall",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_heating_seasonal_performance_factor": 7.4,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "ThroughWall",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_heating_seasonal_performance_factor": 7.4,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": 3.3,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 9999999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": 3.2,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 7.7,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2013 Table 6.8.1-2, Before 1/1/2015"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 7.7,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2013 Table 6.8.1-2, Before 1/1/2015"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "ThroughWall",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_heating_seasonal_performance_factor": 7.4,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2013 Table 6.8.1-2"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "ThroughWall",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_heating_seasonal_performance_factor": 7.4,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2013 Table 6.8.1-3"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "SmallDuctHighVelocity",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 6.8,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2013 Table 6.8.1-4"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": 3.3,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2013 Table 6.8.1-5"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 9999999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": 3.2,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From 90.1-2013 Table 6.8.1-6"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 8.2,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From OEESC2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 8.0,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From OEESC2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "ThroughWall",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_heating_seasonal_performance_factor": 7.4,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From OEESC2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "ThroughWall",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_heating_seasonal_performance_factor": 7.4,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From OEESC2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "SmallDuctHighVelocity",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_heating_seasonal_performance_factor": 6.8,
      "minimum_coefficient_of_performance_heating": null,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From OEESC2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": 3.3,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From OEESC2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 9999999.0,
      "minimum_heating_seasonal_performance_factor": null,
      "minimum_coefficient_of_performance_heating": 3.2,
      "minimum_energy_efficiency_ratio": null,
      "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT",
      "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW",
      "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT",
      "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW",
      "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR",
      "notes": "From OEESC2014 Table 503.2.3(2) Before 1/1/2016"
    }
  ]
}