# Custom changes for the MidriseApartment prototype. # These are changes that are inconsistent with other prototype building types. module MidriseApartment # hvac adjustments specific to the prototype model # # @param model [OpenStudio::Model::Model] OpenStudio model object # @param building_type [String the building type # @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A' # @param prototype_input [Hash] hash of prototype inputs # @return [Boolean] returns true if successful, false if not def model_custom_hvac_tweaks(model, building_type, climate_zone, prototype_input) OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Model', 'Started building type specific adjustments') # adjust the cooling setpoint adjust_clg_setpoint(climate_zone, model) # add elevator and lights&fans for the ground floor corridor add_extra_equip_corridor(model) # add extra infiltration for ground floor corridor add_door_infiltration(climate_zone, model) OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Model', 'Finished building type specific adjustments') return true end # adjust office cooling setpoint in specific climate zones # # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def adjust_clg_setpoint(climate_zone, model) space_name = 'Office' space_type_name = model.getSpaceByName(space_name).get.spaceType.get.name.get thermostat_name = space_type_name + ' Thermostat' thermostat = model.getThermostatSetpointDualSetpointByName(thermostat_name).get case template when '90.1-2004', '90.1-2007', '90.1-2010' case climate_zone when 'ASHRAE 169-2006-0B', 'ASHRAE 169-2006-1B', 'ASHRAE 169-2006-2B', 'ASHRAE 169-2006-3B', 'ASHRAE 169-2013-0B', 'ASHRAE 169-2013-1B', 'ASHRAE 169-2013-2B', 'ASHRAE 169-2013-3B' thermostat.setCoolingSetpointTemperatureSchedule(model_add_schedule(model, 'ApartmentMidRise CLGSETP_OFF_SCH_NO_OPTIMUM')) end end return true end # add elevator and lights&fans for the ground floor corridor # # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def add_extra_equip_corridor(model) corridor_ground_space = model.getSpaceByName('G Corridor').get elec_equip_def1 = OpenStudio::Model::ElectricEquipmentDefinition.new(model) elec_equip_def2 = OpenStudio::Model::ElectricEquipmentDefinition.new(model) elec_equip_def1.setName('Ground Corridor Electric Equipment Definition1') elec_equip_def2.setName('Ground Corridor Electric Equipment Definition2') case template when '90.1-2004', '90.1-2007', '90.1-2010', '90.1-2013', '90.1-2016', '90.1-2019' elec_equip_def1.setFractionLatent(0) elec_equip_def1.setFractionRadiant(0) elec_equip_def1.setFractionLost(0.95) elec_equip_def2.setFractionLatent(0) elec_equip_def2.setFractionRadiant(0) elec_equip_def2.setFractionLost(0.95) elec_equip_def1.setDesignLevel(16_055) if template == '90.1-2013' || template == '90.1-2016' || template == '90.1-2019' elec_equip_def2.setDesignLevel(63) elsif template == '90.1-2010' elec_equip_def2.setDesignLevel(105.9) else elec_equip_def2.setDesignLevel(161.9) end # Create the electric equipment instance and hook it up to the space type elec_equip1 = OpenStudio::Model::ElectricEquipment.new(elec_equip_def1) elec_equip2 = OpenStudio::Model::ElectricEquipment.new(elec_equip_def2) elec_equip1.setName('G Corridor_Elevators_Equip') elec_equip2.setName('Elevators_Lights_Fan') elec_equip1.setSpace(corridor_ground_space) elec_equip2.setSpace(corridor_ground_space) elec_equip1.setSchedule(model_add_schedule(model, 'ApartmentMidRise BLDG_ELEVATORS')) case template when '90.1-2004', '90.1-2007' elec_equip2.setSchedule(model_add_schedule(model, 'ApartmentMidRise ELEV_LIGHT_FAN_SCH_24_7')) when '90.1-2010', '90.1-2013', '90.1-2016', '90.1-2019' elec_equip2.setSchedule(model_add_schedule(model, 'ApartmentMidRise ELEV_LIGHT_FAN_SCH_ADD_DF')) end when 'DOE Ref Pre-1980', 'DOE Ref 1980-2004' elec_equip_def1.setDesignLevel(16_055) elec_equip_def1.setFractionLatent(0) elec_equip_def1.setFractionRadiant(0) elec_equip_def1.setFractionLost(0.95) # Create the electric equipment instance and hook it up to the space type elec_equip1 = OpenStudio::Model::ElectricEquipment.new(elec_equip_def1) elec_equip1.setName('G Corridor_Elevators_Equip') elec_equip1.setSpace(corridor_ground_space) elec_equip1.setSchedule(model_add_schedule(model, 'ApartmentMidRise BLDG_ELEVATORS Pre2004')) end return true end # add extra infiltration for ground floor corridor # # @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A' # @param model [OpenStudio::Model::Model] OpenStudio model object # @return [Boolean] returns true if successful, false if not def add_door_infiltration(climate_zone, model) return false if template == 'DOE Ref 1980-2004' || template == 'DOE Ref Pre-1980' g_corridor = model.getSpaceByName('G Corridor').get infiltration_g_corridor_door = OpenStudio::Model::SpaceInfiltrationDesignFlowRate.new(model) infiltration_g_corridor_door.setName('G Corridor door Infiltration') infiltration_g_corridor_door.setSpace(g_corridor) case template when '90.1-2004' infiltration_g_corridor_door.setDesignFlowRate(0.520557541) infiltration_g_corridor_door.setSchedule(model_add_schedule(model, 'ApartmentMidRise INFIL_Door_Opening_SCH_2004_2007')) when '90.1-2007' case climate_zone when 'ASHRAE 169-2006-0A', 'ASHRAE 169-2006-1A', 'ASHRAE 169-2006-0B', 'ASHRAE 169-2006-1B', 'ASHRAE 169-2006-2A', 'ASHRAE 169-2006-2B', 'ASHRAE 169-2013-0A', 'ASHRAE 169-2013-1A', 'ASHRAE 169-2013-0B', 'ASHRAE 169-2013-1B', 'ASHRAE 169-2013-2A', 'ASHRAE 169-2013-2B' infiltration_g_corridor_door.setDesignFlowRate(0.520557541) else infiltration_g_corridor_door.setDesignFlowRate(0.327531218) end infiltration_g_corridor_door.setSchedule(model_add_schedule(model, 'ApartmentMidRise INFIL_Door_Opening_SCH_2004_2007')) when '90.1-2010', '90.1-2013', '90.1-2016', '90.1-2019' case climate_zone when 'ASHRAE 169-2006-0A', 'ASHRAE 169-2006-1A', 'ASHRAE 169-2006-0B', 'ASHRAE 169-2006-1B', 'ASHRAE 169-2006-2A', 'ASHRAE 169-2006-2B', 'ASHRAE 169-2013-0A', 'ASHRAE 169-2013-1A', 'ASHRAE 169-2013-0B', 'ASHRAE 169-2013-1B', 'ASHRAE 169-2013-2A', 'ASHRAE 169-2013-2B' infiltration_g_corridor_door.setDesignFlowRate(0.520557541) else infiltration_g_corridor_door.setDesignFlowRate(0.327531218) end infiltration_g_corridor_door.setSchedule(model_add_schedule(model, 'ApartmentMidRise INFIL_Door_Opening_SCH_2010_2013')) end # Door infiltration in model not impacted by wind or temperature infiltration_g_corridor_door.setConstantTermCoefficient(1.0) infiltration_g_corridor_door.setTemperatureTermCoefficient(0.0) infiltration_g_corridor_door.setVelocityTermCoefficient(0.0) infiltration_g_corridor_door.setVelocitySquaredTermCoefficient(0.0) return true end # swh adjustments specific to the prototype model # # @param model [OpenStudio::Model::Model] OpenStudio model object # @param building_type [String the building type # @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A' # @param prototype_input [Hash] hash of prototype inputs # @return [Boolean] returns true if successful, false if not def model_custom_swh_tweaks(model, building_type, climate_zone, prototype_input) return true end # geometry adjustments specific to the prototype model # # @param model [OpenStudio::Model::Model] OpenStudio model object # @param building_type [String the building type # @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A' # @param prototype_input [Hash] hash of prototype inputs # @return [Boolean] returns true if successful, false if not def model_custom_geometry_tweaks(model, building_type, climate_zone, prototype_input) # Set original building North axis OpenstudioStandards::Geometry.model_set_building_north_axis(model, 0.0) return true end end