Sha256: 66b339b48785d14b0841b2384af2e18566efae2457b1848236a8135b4cc0c63e
Contents?: true
Size: 1.46 KB
Versions: 19
Compression:
Stored size: 1.46 KB
Contents
class ASHRAE9012007 < ASHRAE901 # @!group FanConstantVolume # Determine the prototype fan pressure rise for a constant volume fan on an AirLoopHVAC based on system airflow. # Defaults to the logic from ASHRAE 90.1-2004 prototypes. # # @param fan_constant_volume [OpenStudio::Model::FanConstantVolume] constant volume fan object # @return [Double] pressure rise in inches H20 def fan_constant_volume_airloop_fan_pressure_rise(fan_constant_volume) # Get the max flow rate from the fan. maximum_flow_rate_m3_per_s = nil if fan_constant_volume.maximumFlowRate.is_initialized maximum_flow_rate_m3_per_s = fan_constant_volume.maximumFlowRate.get elsif fan_constant_volume.autosizedMaximumFlowRate.is_initialized maximum_flow_rate_m3_per_s = fan_constant_volume.autosizedMaximumFlowRate.get else OpenStudio.logFree(OpenStudio::Warn, 'openstudio.prototype.FanConstantVolume', "For #{fan_constant_volume.name} max flow rate is not available, cannot apply prototype assumptions.") return false end # Convert max flow rate to cfm maximum_flow_rate_cfm = OpenStudio.convert(maximum_flow_rate_m3_per_s, 'm^3/s', 'cfm').get # Determine the pressure rise pressure_rise_in_h2o = if maximum_flow_rate_cfm < 7437 2.5 else # Over 7,437 cfm 4.09 end return pressure_rise_in_h2o end end
Version data entries
19 entries across 19 versions & 1 rubygems