# Custom changes for the QuickServiceRestaurant prototype. # These are changes that are inconsistent with other prototype # building types. module SmallDataCenterLowITE def model_custom_hvac_tweaks(building_type, climate_zone, prototype_input, model) OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Model', 'Started building type specific adjustments') add_data_center_load(model) OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Model', 'Finished building type specific adjustments') return true end # add IT equipment (ITE object) for data center building types # Normal electric equipment has been added in model_add_load prior to this # will replace with ITE object here def add_data_center_load(model) model.getSpaceTypes.each do |space_type| # Get the standards data space_type_properties = space_type_get_standards_data(space_type) elec_equip_have_info = false elec_equip_per_area = space_type_properties['electric_equipment_per_area'].to_f elec_equip_sch = space_type_properties['electric_equipment_schedule'] elec_equip_have_info = true unless elec_equip_per_area.zero? # The way ITE object is designed can't input the CPU load and IT fan power separately # calculation below is to indirectly address this total_power_input_per_area = elec_equip_per_area.to_f * (1 + 0.4) # assuming IT fan power is 0.4 of total CPU load it_fan_power_ratio = elec_equip_per_area.to_f * 0.4/total_power_input_per_area if (space_type.name.get.downcase.include?('computer')) || (space_type.name.get.downcase.include?('datacenter')) if elec_equip_have_info it_equipment_def = OpenStudio::Model::ElectricEquipmentITEAirCooledDefinition.new(model) it_equipment_def.setName("IT equipment def") it_equipment_def.setWattsperZoneFloorArea(OpenStudio.convert(total_power_input_per_area.to_f, 'W/ft^2', 'W/m^2').get) it_equipment_def.setDesignFanAirFlowRateperPowerInput(0.0001*(1-it_fan_power_ratio)) it_equipment_def.setDesignFanPowerInputFraction(it_fan_power_ratio) it_equipment_def.setDesignEnteringAirTemperature(27) # recommended SAT 18-27C, use the middle T as design it_equipment_def.setAirFlowCalculationMethod("FlowControlWithApproachTemperatures") # TODO Set the approach temperatures based on CFD simulation results it_equipment_def.setSupplyTemperatureDifference(8.9) # This is under fully open configuration assumption, based on the lookup table in scorecard it_equipment_def.setReturnTemperatureDifference(-7.2) # This is under fully open configuration assumption, based on the lookup table in scorecard it_equipment = OpenStudio::Model::ElectricEquipmentITEAirCooled.new(it_equipment_def) it_equipment.setSpaceType(space_type) it_equipment.setName("#{space_type.name.to_s} IT equipment") unless elec_equip_sch.nil? it_equipment.setDesignPowerInputSchedule(model_add_schedule(model, elec_equip_sch)) OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.SpaceType', "#{space_type.name} set Design Power Input Schedule to #{elec_equip_sch}.") end it_equipment.setCPULoadingSchedule(model.alwaysOnDiscreteSchedule) end end end # remove normal electric equipment model.getElectricEquipments.each(&:remove) end def model_custom_swh_tweaks(model, building_type, climate_zone, prototype_input) return true end def model_custom_geometry_tweaks(building_type, climate_zone, prototype_input, model) return true end end