class ASHRAE9012013 < ASHRAE901 # @!group FanVariableVolume # The threhold horsepower below which part load control is not required. # Per 90.1-2013, table 6.5.3.2.1: the fan motor size for chiller-water # and evaporative cooling is 0.25 hp as of 1/1/2014 instead of 5 hp # # @param fan_variable_volume [OpenStudio::Model::FanVariableVolume] the fan # @return [Double] the limit, in horsepower. Return nil for no limit by default. def fan_variable_volume_part_load_fan_power_limitation_hp_limit(fan_variable_volume) hp_limit = case fan_variable_volume_cooling_system_type(fan_variable_volume) when 'dx' 0.0 when 'chw' 0.25 when 'evap' 0.25 end return hp_limit end # The threhold capacity below which part load control is not required. # Per 90.1-2013, table 6.5.3.2.1: the cooling capacity threshold is 75000 # instead of 110000 as of 1/1/2014 # # @param fan_variable_volume [OpenStudio::Model::FanVariableVolume] the fan # @return [Double] the limit, in Btu/hr. Return nil for no limit by default. def fan_variable_volume_part_load_fan_power_limitation_capacity_limit(fan_variable_volume) cap_limit_btu_per_hr = case fan_variable_volume_cooling_system_type(fan_variable_volume) when 'dx' 110_000 end return cap_limit_btu_per_hr end end