Contents
class ASHRAE9012007 < ASHRAE901 # @!group Pump # Determine type of pump part load control type # # @code_sections [90.1-2007_6.5.4.1] # @param pump [OpenStudio::Model::PumpVariableSpeed] OpenStudio pump object # @param plant_loop_type [String] Type of plant loop # @param pump_nominal_hp [Float] Pump nominal horsepower # @return [String] Pump part load control type def pump_variable_speed_get_control_type(pump, plant_loop_type, pump_nominal_hp) threshold = 50 # hp # Sizing factor to take into account that pumps # are typically sized to handle a ~10% pressure # increase and ~10% flow increase. design_sizing_factor = 1.25 # Get pump head in Pa pump_head_pa = pump.ratedPumpHead if pump_nominal_hp * design_sizing_factor > threshold && pump_head_pa > 300_000 # 100 ft. of head return 'VSD No Reset' else return 'Riding Curve' end end end