  "heat_pumps": [
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 65000.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 65000.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 65000.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 65000.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65001.0,
      "maximum_capacity": 136480.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.26,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65001.0,
      "maximum_capacity": 136480.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.08,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65001.0,
      "maximum_capacity": 136480.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.26,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65001.0,
      "maximum_capacity": 136480.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.08,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 136481.0,
      "maximum_capacity": 238840.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 136481.0,
      "maximum_capacity": 238840.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.72,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 136841.0,
      "maximum_capacity": 238840.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 136841.0,
      "maximum_capacity": 238840.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.72,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 238841.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 7.94,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 238841.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 7.76,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 238841.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 7.94,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": "From NECB 2011, Table 5.2.12.1"
    },
    {
      "template": "NECB 2011",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 238841.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 7.76,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
      "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
      "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
      "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
      "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
      "notes": null
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": null,
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "ThroughWall",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "ThroughWall",
      "heating_type": null,
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": null,
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "ThroughWall",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "ThroughWall",
      "heating_type": null,
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref 1980-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": null,
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "ThroughWall",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "ThroughWall",
      "heating_type": null,
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2004",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 Table 6.8.1B"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": null,
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "ThroughWall",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_seasonal_efficiency": 10.9,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "ThroughWall",
      "heating_type": null,
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_seasonal_efficiency": 10.6,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2007",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": null,
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "ThroughWall",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "ThroughWall",
      "heating_type": null,
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.2,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.2,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.0,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.0,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.7,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.7,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.4,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.5,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.4,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.5,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.6,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.6,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.4,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2010",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.4,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1B"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": null,
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 13.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "ThroughWall",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "ThroughWall",
      "heating_type": null,
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 11.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.2,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.2,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.0,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.0,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.7,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.7,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.4,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.5,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.4,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.5,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.6,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.6,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.4,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "90.1-2013",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.4,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": null,
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 14.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "ThroughWall",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "ThroughWall",
      "heating_type": null,
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "minimum_seasonal_efficiency": 12.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": null,
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "minimum_seasonal_efficiency": 11.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.2,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 11.0,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.2,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.0,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.8,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 11.0,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.7,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.6,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.7,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.4,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.5,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.4,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 10.5,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.6,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.5,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.6,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.4,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    },
    {
      "template": "OEESC 2014",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": 9.4,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
    }
  ]
}