  "economizers": [
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-1A",
      "data_center": false,
      "capacity_limit": null,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-1A",
      "data_center": true,
      "capacity_limit": null,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-1B",
      "data_center": false,
      "capacity_limit": null,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-1B",
      "data_center": true,
      "capacity_limit": null,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-2A",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-2A",
      "data_center": true,
      "capacity_limit": null,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-2B",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-2B",
      "data_center": true,
      "capacity_limit": 135000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-3A",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-3A",
      "data_center": true,
      "capacity_limit": null,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-3B",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-3B",
      "data_center": true,
      "capacity_limit": 65000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-3C",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-3C",
      "data_center": true,
      "capacity_limit": 65000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-4A",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-4A",
      "data_center": true,
      "capacity_limit": null,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-4B",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-4B",
      "data_center": true,
      "capacity_limit": 65000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-4C",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-4C",
      "data_center": true,
      "capacity_limit": 65000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-5A",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 70.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-5A",
      "data_center": true,
      "capacity_limit": 135000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 70.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-5B",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-5B",
      "data_center": true,
      "capacity_limit": 65000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-5C",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-5C",
      "data_center": true,
      "capacity_limit": 65000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-6A",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 70.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-6A",
      "data_center": true,
      "capacity_limit": 135000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 70.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-6B",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-6B",
      "data_center": true,
      "capacity_limit": 65000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-7A",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-7A",
      "data_center": true,
      "capacity_limit": 135000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-7B",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-7B",
      "data_center": true,
      "capacity_limit": 135000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-8A",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-8A",
      "data_center": true,
      "capacity_limit": 135000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-8B",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2006-8B",
      "data_center": true,
      "capacity_limit": 135000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-1A",
      "data_center": false,
      "capacity_limit": null,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-1A",
      "data_center": true,
      "capacity_limit": null,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-1B",
      "data_center": false,
      "capacity_limit": null,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-1B",
      "data_center": true,
      "capacity_limit": null,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-2A",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-2A",
      "data_center": true,
      "capacity_limit": null,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-2B",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-2B",
      "data_center": true,
      "capacity_limit": 135000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-3A",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-3A",
      "data_center": true,
      "capacity_limit": null,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-3B",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-3B",
      "data_center": true,
      "capacity_limit": 65000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-3C",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-3C",
      "data_center": true,
      "capacity_limit": 65000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-4A",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-4A",
      "data_center": true,
      "capacity_limit": null,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-4B",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-4B",
      "data_center": true,
      "capacity_limit": 65000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-4C",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-4C",
      "data_center": true,
      "capacity_limit": 65000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-5A",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 70.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-5A",
      "data_center": true,
      "capacity_limit": 135000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 70.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-5B",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-5B",
      "data_center": true,
      "capacity_limit": 65000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-5C",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-5C",
      "data_center": true,
      "capacity_limit": 65000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-6A",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 70.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-6A",
      "data_center": true,
      "capacity_limit": 135000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 70.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-6B",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-6B",
      "data_center": true,
      "capacity_limit": 65000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-7A",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-7A",
      "data_center": true,
      "capacity_limit": 135000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-7B",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-7B",
      "data_center": true,
      "capacity_limit": 135000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-8A",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-8A",
      "data_center": true,
      "capacity_limit": 135000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-8B",
      "data_center": false,
      "capacity_limit": 54000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1A"
    },
    {
      "template": "90.1-2010",
      "climate_zone": "ASHRAE 169-2013-8B",
      "data_center": true,
      "capacity_limit": 135000.0,
      "fixed_dry_bulb_high_limit_shutoff_temp": 75.0,
      "notes": "90.1-2010 Table 6.5.1B"
    }
  ]
}