{ "tables": { "heat_pumps": { "data_type": "table", "refs": [ "assumption" ], "table": [ { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 65000.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 65000.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 65000.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 65000.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.0, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 65001.0, "maximum_capacity": 136480.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 11, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 65001.0, "maximum_capacity": 136480.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.8, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 65001.0, "maximum_capacity": 136480.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 11, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 65001.0, "maximum_capacity": 136480.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.8, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 136481.0, "maximum_capacity": 238840.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.6, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 136481.0, "maximum_capacity": 238840.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.4, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 136841.0, "maximum_capacity": 238840.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.6, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 136841.0, "maximum_capacity": 238840.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 10.4, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Single Package", "minimum_capacity": 238841.0, "maximum_capacity": 9999999.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.5, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Single Package", "minimum_capacity": 238841.0, "maximum_capacity": 9999999.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "Electric Resistance or None", "subcategory": "Split System", "minimum_capacity": 238841.0, "maximum_capacity": 9999999.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.5, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": "From NECB 2011, Table 5.2.12.1" }, { "template": "NECB2015", "cooling_type": "AirCooled", "heating_type": "All Other", "subcategory": "Split System", "minimum_capacity": 238841.0, "maximum_capacity": 9999999.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_seasonal_efficiency": null, "minimum_full_load_efficiency": 9.3, "minimum_iplv": null, "minimum_integrated_energy_efficiency_ratio": null, "pthp_eer_coefficient_1": null, "pthp_eer_coefficient_2": null, "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT", "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW", "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT", "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW", "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR", "notes": null } ] } } }