# Custom changes for the MediumOffice prototype. # These are changes that are inconsistent with other prototype # building types. module MediumOffice def model_custom_hvac_tweaks(building_type, climate_zone, prototype_input, model) OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Model', 'Started building type specific adjustments') model.getSpaces.sort.each do |space| if space.name.get.to_s == 'Core_bottom' model_add_elevator(model, space, prototype_input['number_of_elevators'], prototype_input['elevator_type'], prototype_input['elevator_schedule'], prototype_input['elevator_fan_schedule'], prototype_input['elevator_fan_schedule'], building_type) end end OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Model', 'Finished building type specific adjustments') # add extra infiltration for entry door add_door_infiltration(climate_zone, model) OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Model', 'Added door infiltration') return true end # add hvac def add_door_infiltration(climate_zone, model) # add extra infiltration for entry door in m3/s (there is no attic in 'DOE Ref Pre-1980') unless template == 'DOE Ref 1980-2004' || template == 'DOE Ref Pre-1980' entry_space = model.getSpaceByName('Perimeter_bot_ZN_1').get infiltration_entrydoor = OpenStudio::Model::SpaceInfiltrationDesignFlowRate.new(model) infiltration_entrydoor.setName('entry door Infiltration') infiltration_per_zone_entrydoor = 0 if template == '90.1-2004' infiltration_per_zone_entrydoor = 1.04300287 infiltration_entrydoor.setSchedule(model_add_schedule(model, 'OfficeMedium INFIL_Door_Opening_SCH')) elsif template == '90.1-2007' || template == '90.1-2010' || template == '90.1-2013' case climate_zone when 'ASHRAE 169-2006-1A', 'ASHRAE 169-2006-2A', 'ASHRAE 169-2006-1B', 'ASHRAE 169-2006-2B' infiltration_per_zone_entrydoor = 1.04300287 infiltration_entrydoor.setSchedule(model_add_schedule(model, 'OfficeMedium INFIL_Door_Opening_SCH')) else infiltration_per_zone_entrydoor = 0.678659786 infiltration_entrydoor.setSchedule(model_add_schedule(model, 'OfficeMedium INFIL_Door_Opening_SCH')) end end infiltration_entrydoor.setDesignFlowRate(infiltration_per_zone_entrydoor) infiltration_entrydoor.setSpace(entry_space) end end def update_waterheater_loss_coefficient(model) case template when '90.1-2004', '90.1-2007', '90.1-2010', '90.1-2013', 'NECB2011' model.getWaterHeaterMixeds.sort.each do |water_heater| water_heater.setOffCycleLossCoefficienttoAmbientTemperature(7.561562668) water_heater.setOnCycleLossCoefficienttoAmbientTemperature(7.561562668) end end end def model_custom_swh_tweaks(model, building_type, climate_zone, prototype_input) update_waterheater_loss_coefficient(model) return true end end