{ "tables": { "heat_pumps_heating": { "data_type": "table", "refs": [ "assumption" ], "table": [ { "cooling_type": "AirCooled", "subcategory": "Single Package", "minimum_capacity": 0.0, "maximum_capacity": 64830.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_heating_seasonal_performance_factor": null, "minimum_coefficient_of_performance_heating": 3.3, "minimum_energy_efficiency_ratio": null, "pthp_cop_coefficient_1": null, "pthp_cop_coefficient_2": null, "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT", "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW", "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT", "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW", "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR", "notes": "From NECB 2020, Table 5.2.12.1.-B" }, { "cooling_type": "AirCooled", "subcategory": "Split System", "minimum_capacity": 0.0, "maximum_capacity": 64830.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_heating_seasonal_performance_factor": null, "minimum_coefficient_of_performance_heating": 3.3, "minimum_energy_efficiency_ratio": null, "pthp_cop_coefficient_1": null, "pthp_cop_coefficient_2": null, "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT", "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW", "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT", "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW", "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR", "notes": "From NECB 2020, Table 5.2.12.1.-B" }, { "cooling_type": "AirCooled", "subcategory": "Single Package", "minimum_capacity": 64831.0, "maximum_capacity": 136485.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_heating_seasonal_performance_factor": null, "minimum_coefficient_of_performance_heating": 3.3, "minimum_energy_efficiency_ratio": null, "pthp_cop_coefficient_1": null, "pthp_cop_coefficient_2": null, "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT", "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW", "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT", "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW", "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR", "notes": "From NECB 2020, Table 5.2.12.1.-A" }, { "cooling_type": "AirCooled", "subcategory": "Split System", "minimum_capacity": 64831.0, "maximum_capacity": 136485.0, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_heating_seasonal_performance_factor": null, "minimum_coefficient_of_performance_heating": 3.3, "minimum_energy_efficiency_ratio": null, "pthp_cop_coefficient_1": null, "pthp_cop_coefficient_2": null, "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT", "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW", "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT", "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW", "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR", "notes": "From NECB 2020, Table 5.2.12.1.-A" }, { "cooling_type": "AirCooled", "subcategory": "Single Package", "minimum_capacity": 136486, "maximum_capacity": 238849, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_heating_seasonal_performance_factor": null, "minimum_coefficient_of_performance_heating": 3.2, "minimum_energy_efficiency_ratio": null, "pthp_cop_coefficient_1": null, "pthp_cop_coefficient_2": null, "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT", "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW", "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT", "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW", "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR", "notes": "From NECB 2020, Table 5.2.12.1.-A" }, { "cooling_type": "AirCooled", "subcategory": "Split System", "minimum_capacity": 136486, "maximum_capacity": 238849, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_heating_seasonal_performance_factor": null, "minimum_coefficient_of_performance_heating": 3.2, "minimum_energy_efficiency_ratio": null, "pthp_cop_coefficient_1": null, "pthp_cop_coefficient_2": null, "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT", "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW", "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT", "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW", "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR", "notes": "From NECB 2020, Table 5.2.12.1.-A" }, { "cooling_type": "AirCooled", "subcategory": "Single Package", "minimum_capacity": 238850, "maximum_capacity": 760907, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_heating_seasonal_performance_factor": null, "minimum_coefficient_of_performance_heating": 3.2, "minimum_energy_efficiency_ratio": null, "pthp_cop_coefficient_1": null, "pthp_cop_coefficient_2": null, "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT", "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW", "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT", "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW", "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR", "notes": "From NECB 2020, Table 5.2.12.1.-A" }, { "cooling_type": "AirCooled", "subcategory": "Split System", "minimum_capacity": 238850, "maximum_capacity": 760907, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_heating_seasonal_performance_factor": null, "minimum_coefficient_of_performance_heating": 3.2, "minimum_energy_efficiency_ratio": null, "pthp_cop_coefficient_1": null, "pthp_cop_coefficient_2": null, "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT", "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW", "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT", "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW", "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR", "notes": "From NECB 2020, Table 5.2.12.1.-A" }, { "cooling_type": "AirCooled", "subcategory": "Single Package", "minimum_capacity": 760908, "maximum_capacity": 9999999, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_heating_seasonal_performance_factor": null, "minimum_coefficient_of_performance_heating": 3.2, "minimum_energy_efficiency_ratio": null, "pthp_cop_coefficient_1": null, "pthp_cop_coefficient_2": null, "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT", "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW", "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT", "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW", "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR", "notes": "From NECB 2020, Table 5.2.12.1.-A" }, { "cooling_type": "AirCooled", "subcategory": "Split System", "minimum_capacity": 760908, "maximum_capacity": 9999999, "start_date": "9/9/1919", "end_date": "2999-09-09T00:00:00+00:00", "minimum_heating_seasonal_performance_factor": null, "minimum_coefficient_of_performance_heating": 3.2, "minimum_energy_efficiency_ratio": null, "pthp_cop_coefficient_1": null, "pthp_cop_coefficient_2": null, "heat_cap_ft": "DXHEAT-NECB2011-REF-CAPFT", "heat_cap_fflow": "DXHEAT-NECB2011-REF-CAPFFLOW", "heat_eir_ft": "DXHEAT-NECB2011-REF-EIRFT", "heat_eir_fflow": "DXHEAT-NECB2011-REF-EIRFFLOW", "heat_plf_fplr": "DXHEAT-NECB2011-REF-PLFFPLR", "notes": "From NECB 2020, Table 5.2.12.1.-A" } ] } } }