  "heat_pumps": [
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 10.0,
      "pthp_eer_coefficient_2": 0.16,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-1989 Table 10-4A"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.9,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 8.8,
      "minimum_iplv": 9.0,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "PTHP",
      "minimum_capacity": 0.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": 10.0,
      "pthp_eer_coefficient_2": 0.16,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-1989 Table 10-4A"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 65000.0,
      "maximum_capacity": 134999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 10.1,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 135000.0,
      "maximum_capacity": 239999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.3,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "AirCooled",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 240000.0,
      "maximum_capacity": 9999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": null,
      "minimum_full_load_efficiency": 9.0,
      "minimum_iplv": 9.2,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "SmallDuctHighVelocity",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 64999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "ThroughWall",
      "heating_type": "All Other",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Single Package",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 9.7,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    },
    {
      "template": "DOE Ref Pre-1980",
      "cooling_type": "ThroughWall",
      "heating_type": "Electric Resistance or None",
      "subcategory": "Split System",
      "minimum_capacity": 0.0,
      "maximum_capacity": 29999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_seasonal_efficiency": 10.0,
      "minimum_full_load_efficiency": null,
      "minimum_iplv": null,
      "minimum_integrated_energy_efficiency_ratio": null,
      "pthp_eer_coefficient_1": null,
      "pthp_eer_coefficient_2": null,
      "cool_cap_ft": "HPACCoolCapFT",
      "cool_cap_fflow": "HPACCoolCapFFF",
      "cool_eir_ft": "HPACCOOLEIRFT",
      "cool_eir_fflow": "HPACCOOLEIRFFF",
      "cool_plf_fplr": "HPACCOOLPLFFPLR",
      "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
    }
  ]
}