  "boilers": [
    {
      "template": "90.1-2016",
      "fluid_type": "Hot Water",
      "fuel_type": "Gas",
      "condensing": null,
      "condensing_control": null,
      "minimum_capacity": 0.0,
      "maximum_capacity": 299999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_annual_fuel_utilization_efficiency": 0.82,
      "minimum_thermal_efficiency": null,
      "minimum_combustion_efficiency": null,
      "efffplr": "Boiler with No Minimum Turndown",
      "notes": "From 90.1-2016"
    },
    {
      "template": "90.1-2016",
      "fluid_type": "Hot Water",
      "fuel_type": "Gas",
      "condensing": null,
      "condensing_control": null,
      "minimum_capacity": 300000.0,
      "maximum_capacity": 999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_annual_fuel_utilization_efficiency": null,
      "minimum_thermal_efficiency": 0.8,
      "minimum_combustion_efficiency": null,
      "efffplr": "Boiler with No Minimum Turndown",
      "notes": "From 90.1-2016"
    },
    {
      "template": "90.1-2016",
      "fluid_type": "Hot Water",
      "fuel_type": "Gas",
      "condensing": null,
      "condensing_control": null,
      "minimum_capacity": 1000000.0,
      "maximum_capacity": 249999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_annual_fuel_utilization_efficiency": null,
      "minimum_thermal_efficiency": 0.8,
      "minimum_combustion_efficiency": null,
      "efffplr": "Boiler with Minimum Turndown",
      "notes": "From 90.1-2016"
    },
    {
      "template": "90.1-2016",
      "fluid_type": "Hot Water",
      "fuel_type": "Gas",
      "condensing": null,
      "condensing_control": null,
      "minimum_capacity": 250000000.0,
      "maximum_capacity": 9999999999.0,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_annual_fuel_utilization_efficiency": null,
      "minimum_thermal_efficiency": null,
      "minimum_combustion_efficiency": 0.82,
      "efffplr": "Boiler with Minimum Turndown",
      "notes": "From 90.1-2016"
    }
  ]
}