  "heat_rejection": [
    {
      "template": "90.1-2013",
      "equipment_type": "Closed Cooling Tower",
      "fan_type": "Centrifugal",
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance": 7.0
    },
    {
      "template": "90.1-2013",
      "equipment_type": "Closed Cooling Tower",
      "fan_type": "Propeller or Axial",
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance": 14.0
    },
    {
      "template": "90.1-2013",
      "equipment_type": "Dry Cooler",
      "fan_type": "Propeller or Axial",
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance": 4.0
    },
    {
      "template": "90.1-2013",
      "equipment_type": "Open Cooling Tower",
      "fan_type": "Centrifugal",
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance": 20.0
    },
    {
      "template": "90.1-2013",
      "equipment_type": "Open Cooling Tower",
      "fan_type": "Propeller or Axial",
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance": 40.2
    }
  ]
}

Version data entries

3 entries across 3 versions & 1 rubygems

Version Path
openstudio-standards-0.2.14 data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.heat_rejection.json
openstudio-standards-0.2.13 data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.heat_rejection.json
openstudio-standards-0.2.13.rc3 data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.heat_rejection.json