{ "heat_rejection": [ { "template": "DOE Ref Pre-1980", "equipment_type": "Closed Cooling Tower", "fan_type": "Centrifugal", "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": 20.0, "notes": "From 90.1-2004 Table 6.8.1G" }, { "template": "DOE Ref Pre-1980", "equipment_type": "Closed Cooling Tower", "fan_type": "Propeller or Axial", "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": 38.2, "notes": "From 90.1-2004 Table 6.8.1G" }, { "template": "DOE Ref Pre-1980", "equipment_type": "Dry Cooler", "fan_type": "Propeller or Axial", "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": 4.0, "notes": "Not required by code. Value provided by 90.1 Mechanical Subcommittee" }, { "template": "DOE Ref Pre-1980", "equipment_type": "Open Cooling Tower", "fan_type": "Centrifugal", "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": 20.0, "notes": "From 90.1-2004 Table 6.8.1G" }, { "template": "DOE Ref Pre-1980", "equipment_type": "Open Cooling Tower", "fan_type": "Propeller or Axial", "start_date": "1919-09-09T00:00:00+00:00", "end_date": "2999-09-09T00:00:00+00:00", "minimum_performance_gpm_per_hp": 38.2, "notes": "From 90.1-2004 Table 6.8.1G" } ] }