  "heat_rejection": [
    {
      "equipment_type": "Open Cooling Tower",
      "fan_type": "Centrifugal",
      "test_fluid": null,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance_gpm_per_hp": 20,
      "minimum_performance_btu_per_hr_per_hp": null
    },
    {
      "equipment_type": "Open Cooling Tower",
      "fan_type": "Propeller or Axial",
      "test_fluid": null,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance_gpm_per_hp": 38.2,
      "minimum_performance_btu_per_hr_per_hp": null
    },
    {
      "equipment_type": "Closed Cooling Tower",
      "fan_type": "Centrifugal",
      "test_fluid": null,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance_gpm_per_hp": 20,
      "minimum_performance_btu_per_hr_per_hp": null
    },
    {
      "equipment_type": "Closed Cooling Tower",
      "fan_type": "Propeller or Axial",
      "test_fluid": null,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance_gpm_per_hp": 38.2,
      "minimum_performance_btu_per_hr_per_hp": null
    },
    {
      "equipment_type": "Air Cooled Condensers",
      "fan_type": null,
      "test_fluid": null,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance_gpm_per_hp": null,
      "minimum_performance_btu_per_hr_per_hp": 176000
    },
    {
      "equipment_type": "Dry Cooler",
      "fan_type": "Propeller or Axial",
      "test_fluid": null,
      "start_date": "1919-09-09T00:00:00+00:00",
      "end_date": "2999-09-09T00:00:00+00:00",
      "minimum_performance_gpm_per_hp": 4,
      "minimum_performance_btu_per_hr_per_hp": null
    }
  ]
}

Version data entries

12 entries across 6 versions & 1 rubygems

Version Path
openstudio-standards-0.7.1 lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.heat_rejection.json
openstudio-standards-0.7.1 lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.heat_rejection.json
openstudio-standards-0.7.0 lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.heat_rejection.json
openstudio-standards-0.7.0 lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.heat_rejection.json
openstudio-standards-0.7.0.rc1 lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.heat_rejection.json
openstudio-standards-0.7.0.rc1 lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.heat_rejection.json
openstudio-standards-0.6.3 lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.heat_rejection.json
openstudio-standards-0.6.3 lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.heat_rejection.json
openstudio-standards-0.6.0.rc2 lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.heat_rejection.json
openstudio-standards-0.6.0.rc2 lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.heat_rejection.json
openstudio-standards-0.6.0.rc1 lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.heat_rejection.json
openstudio-standards-0.6.0.rc1 lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.heat_rejection.json